EN
blueplanet hybrid 10.0 TL3
Page 50
A112
PE connection on device
unavailable
The PE connection is not connected to the device
or it has been incorrectly connected. Check the
installation.
A120
Setting parameters
The device could not be configured from
EEPROM. Contact Service.
Note: During commissioning, the grid operator
settings must be made once in the hy-sys soft-
ware.
A121
A122
Setting parameters
EEPROM can not be written because not enough
supply voltage is available. Make sure that the PV
voltage amounts to at least 240V.
A123
A124
Setting parameters
The EEPRPOM cannot be read. Contact Service.
A125
Unsaved changes
Settings have been made on the device, but have
not yet been saved. If necessary, the settings can
be saved under
User Settings
.
A130
Check supply settings
Check the Pav,e and P_feed_in_limit settings. The
fault will occur if P_feed_in_limit is > Pav,e.
A131
Power limitation
The device limits the output power as the device
is too warm.
A132
Power limitation
The device limits the output power according to
the specified characteristic curve P(U).
A133
Power limitation
The device limits the output power according to
the specified characteristic curve P(f).
A200
Battery: Undervoltage
The connected battery has a voltage < 96V
A240
Battery communication
The device cannot communicate with the battery.
Check the communication connection to the bat-
tery, including the pertinent software settings.
A250
Battery wiring fault
The measured battery voltage does not corre-
spond with the battery voltage determined in the
BCU (Battery Control Unit).
A260
Battery not found
The device cannot communicate with the battery.
Check the communication connection to the bat-
tery, including the pertinent software settings.