KACO blue-
planet 87.0
TL3 M1 WM
OD IIF0
KACO blue-
planet 92.0
TL3 M1 WM
OD IIG0
KACO blue-
planet 110
TL3 M1 WM
OD IIK0
KACO blue-
planet 125
TL3 M1 WM
OD IIP0
KACO blue-
planet 137
TL3 M1 WM
OD IIP0
KACO blue-
planet 150
TL3 M1 WM
OD IIQ0
Initial short-circuit alternat-
ing current (Ik" first single pe-
riod effective value)
137 A
Short circuit current continu-
ous [ms] (max output fault
current)
134 A
Inrush current
5 A [RMS (20ms)]
Rated frequency
50/60 Hz
Frequency range
45 - 65 Hz
Reactive power
0-100 % Snom
cos phi
1 - 0.3 ind/cap
Number of feed-in phases
3
Distortion factor (THD)
< 3 %
< 3 %
< 3 %
3 %
2.8 %
< 3 %
Max. voltage range (up to
100 s)
475 V
500 V
600 V
750 V
825 V
AC overvoltage protection
Base
4.2
General data
KACO blue-
planet 87.0
TL3 M1 WM
OD IIF0
KACO blue-
planet 92.0
TL3 M1 WM
OD IIG0
KACO blue-
planet 110
TL3 M1 WM
OD IIK0
KACO blue-
planet 125
TL3 M1 WM
OD IIP0
KACO blue-
planet 137
TL3 M1 WM
OD IIP0
KACO blue-
planet 150
TL3 M1 WM
OD IIQ0
General electrical data
Max. efficiency
99.0 %
98.8 %
99.1 %
99.2 %
European efficiency
98.6 %
98.5 %
98.8 %
99.0 %
Self consumption: Standby
< 10 W
Feed-in from
> 200 W
Transformer unit
no
Protection class / over volt-
age category
I / III
Grid monitoring
Country-specific
Distribution system
TN-C system, TT system, Solid grounded wye
General data
Display
LEDs
Control elements / operating
control
Button / web server
Menu language
EN; DE; FR; IT; ES; PL; NL; PT; CZ; HU; SL; TR; RO
Interfaces
2 x Ethernet, USB, 2x RS485 (1x reserviert für Stringcombiner Kom.), optional
Fault signal relay
yes (integrated switch)
DC switch / AC switch
no / yes (XL version) / no
Cooling
temp. regulated fan, max air throughput 364 m³/h
Number of fans
3x outside, 1x inside
Noise emission
<60 db(A)
Housing material
AL
H x W x D
28,30 inch x 28,30 inch x 18,11 inch
Weight
172 Ib
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 12