Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Maximum apparent
power Slim
1000 – S
max
[VA]
NOTE: The max. apparent power limits the internal power of the de-
vice.
More detailed information at:
Other grid support functions effective on active power [See sec-
tion 10.4
F
Enter the value or set the value using the slider.
The apparent power is limited globally to the configured value in VA. All
active and reactive power control values use S
lim
instead of S
max
as
100 %, if S
lim
is configured.
4
1
2
3
4
Maximum active power
Plim
1.0 - 100.0 [% Slim]
Password protection
Status
More detailed information at:
Other grid support functions effective on active power [See sec-
tion 10.4
F
Enter the value or set the value using the slider.
Active power is limited globally to the configured value in % S
lim
or S
max
.
1 Optional: Activate password protection.
2 Confirm the action field.
4
1
2
3
4
External
NOTE: The output power of the device can be set permanently to a
lower value than the maximum output power by the external power
limitation.
Power limitation
Status
F
Specify the activation status.
AC fallback active
power
0 – 100 [%Plim]
F
Set fallback power.
Specifies the standard power in the event of a communication failure. If
no active power command is received within the configured timeout,
the inverter sets the power to the configured fallback power.
Fallback time
60 – 43200 [s]
F
Set the fallback time.
Specifies the timeout time after which the inverter sets the fallback
power in the event of a communication failure.
4
1
2
3
4
Increasing output gra-
dient & Decreasing
output gradient
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Settling time
200 – 30000 [ms]
Password protection
Status
1 Specify the settling time.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
Reactive Power Control
(RPC)
NOTE: Activate the reactive power process in the mode menu.
4
1
2
3
4
Mode
Cos-phi const. | Q
const. | Cos-phi(P/Pn)
| Q(U)
Password protection
Status
Reactive power control [See section 10.1
1 Select a control process.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
Cos-phi constant
Define cos φ constant.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 57