Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
P(U) operation mode
Off | On
F
Activate the control process.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
4
1
2
3
4
Reference power
Instantaneous
power | Nominal
power
F
Select the power-dependent control method.
4
1
2
3
4
Rated voltage
Maximum phase
voltage | Positive
phase sequence volt-
age
F
Select the voltage to be rated.
Defines which voltage in a three-phase system is to be evaluated.
4
1
2
3
4
Hysteresis mode
Off | On
NOTE: Hysteresis mode affects the shutdown response of P(U).
F
Activate the mode.
4
1
2
3
4
Deactivation gradient
0 – 65534 [% / min]
F
Set the gradients for the power limitation.
4
1
2
3
4
Deactivation time
0 – 60000000 [ms]
F
Specify the time for voltage reduction.
4
1
2
3
4
Increasing output gra-
dient & Decreasing
output gradient
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Settling time
200 – 120000 [ms]
F
Specify the settling time.
4
1
2
3
4
Active curve
1 - 5
F
Select the active curve.
NOTE: Up to 5 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
4
1
2
3
4
Number of nodes
2 – 5
F
Specify the number of nodes.
Power
0.0 – 100.0 [%]
F
Specify power for 1st, 5th ... node as a percentage of the maximum
power.
Voltage
0.0 – 126.0 [%]
Password protection
Status
1 Specify voltage for 1st, 5th ... node as a percentage of the maximum
voltage.
2 Activate optional password protection.
3 Confirm the action field.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 62