Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Grid Parameters
Input screens for network parameters
4
1
2
3
4
Country & Grid type
NOTE: This option influences the country-specific operating settings of
the device. Please consult KACO Service for further information.
NOTE: Configuration:.
Configuration via web user interface [See sec-
F
Select country and grid type.
Nominal grid voltage &
Nominal grid frequency
Password protection
Status
F
Specify optional nominal grid voltage.
NOTE: The device switches off if the grid frequency deviates from the
nominal grid voltage by more than 9.5Hz.
1 Select optional nominal grid frequency.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
3-phase monitoring
On / Off
NOTE: The device is equipped with redundant 3-phase monitoring. If
the grid voltage exceeds or drops below the configured values, the de-
vice switches off. The minimum switch-off threshold can be set in 1 V
increments.
F
Activate or disable monitoring.
4
1
2
3
4
FRT (Fault Ride
Through)
NOTE: The device supports dynamic grid stabilization (Fault Ride-
Through)
4
1
2
3
4
Operating mode –
On | Off
F
Select a control process.
On: Activates dynamic grid support using dynamic reactive current.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
Settings | Manual |Pre-
defined zero current
F
Select a control process.
Priority – Reactive cur-
rent limitation | Dy-
namic reactive current
F
Select a control process.
4
1
2
3
4
Constant k positive se-
quence dip &
Constant k positive se-
quence swell
k 0 – 10 2
F
Set amplification factor k for the pos. sequence for drop and increase
in the grid voltage.
4
1
2
3
4
Constant k negative se-
quence dip
Constant k negative se-
quence swell
k 0 – 10 2
F
Set amplification factor k for the neg. sequence for drop and increase
in the grid voltage.
4
1
2
3
4
Dead band
0 - 100 [% Uref]
10.0
F
Set dead band in %.
4
1
2
3
4
Dynamic reactive cur-
rent only
Off | On
NOTE: With FRT mode activated, the pre-fault reactive current can be
added.
F
If necessary, activate pre-fault reactive current.