Kaba ILCO RAC 660G Installation Manual Download Page 7

PK3512_09_07 • REMOTE ACCESS CONTROLLER - 660G

7

4.0 System Installation Overview

NOTES: 

•   For Installation of the keypad readers refer to the manufactures 

installation instructions.

•   The RAC 660G provides ingress (entry) access to locations 

where stand alone locking devices cannot be used.

4.1 Pre-Installation Procedures

Before starting: 
•   Ensure that all cabling is available for the required wiring 

of  peripherals  as  indicated  in  the  instructions  supplied 
with each product to be connected.

•   Be sure to have all tools listed on the tool list in section 3.1.
•   Be sure to have every component available as ordered for 

the RAC 660G system being installed, refer to the parts 
list in section 3.1.

Step 1:  Identify secure location for the 

controller box 

Important:  Access to the control panel must be restricted 
to authorized personnel only. (ex: service)

!

Important:   If no AC power source is available near the 
desired control box location, a certified electrician must 
install an electrical outlet within 6 ft max of the  
RAC 660G system.

!

•   If  possible,  the  control  panel  should  be  mounted  at  a 

workable  height  with  clearance  to  completely  open  the 
access panel near an unswitched AC power source.

•   Make sure that the controller box can be secured to the 

wall or ceiling using the screws and anchors provided in 
the hardware bag. 

•   The controller box can be either placed horizontally in the 

ceiling or vertically on a concrete, wood, or plaster wall.

•   The temperature in the chosen location must be between 

32°F to 120°F (0°C to 49°C).

•   The controller box must be in a location sheltered against 

exterior  elements,  weather  hazards  and  dripping 
wate

r.

•   Do  not  use  cord  and  wall  outlets  for  mounting  of  the 

controller box. The unit must be fixed with the hardware 
supplied.

Step 2:  Identify location(s) for the keypad 

reader and required peripherals

Important:  All peripherals used by any RAC 660G user 
must be placed at standard height, prescribed by any 
local building legislation or regulations.

!

For ingress function, the keypad readers must be placed 

within 100 

feet (30m)

 from the controller box. The keypad should be installed 

near the access door it controls at user’s height. The location should 
be obvious and ergonomically efficient to any user.

Keypad:

The space to use the keypad reader must be large enough to 
allow adequate clearance.

Remaining peripherals:

Determine the location required for any other RAC 660G system 
peripherals (REX button, remote unlock, etc) and ensure that all 
required cabling is available as needed.

Step 3: Set the desired access delay

The RAC 660G system factory default setting for the delay on 
access devices is 3 seconds. To change the value configure 
the controller board (B) dipswitch SW2 settings as per Annex 
A, Table 3.

Step 4: Install strain relief

One strain relief (Q) is provided in the hardware bag to secure 
the wires leading into the controller box and help prevent the 
possibility of wire tampering.

Compression 
Nut

Q

Figure 8

NOTE: 

 The strain relief (Q) provided in the hardware bag has 
an  opening  diameter  that  is  variable  to  allow  for  a 
variety of wires to be routed into the controller box. Do 
not attempt to route an excessive amount of wires. If 
extra strain relief(s) is required please contact Kaba.

Summary of Contents for ILCO RAC 660G

Page 1: ...INSTALLATION GUIDE Remote Access Controller 660G PK3512 ...

Page 2: ...ntroller box 7 Step 2 Identify location s for the keypad reader and required peripherals 7 Step 3 Set the desired access delay 7 Step 4 Install strain relief 7 4 2 Installation Procedures 8 Step 5 Mounting the controller box 8 Step 6 Connect wiring 9 Step 7 Mounting wiring keypad reader 9 Step 8 Install strain relief bushing 10 Step 9 Completing the installation 10 5 0 Settings and Operation 11 5 ...

Page 3: ...0 906 4526 OR Visit the Kaba Support Website http connect kabalodging com Warnings and Cautions Please read and follow all directions carefully Important Carefully inspect windows doorframe door etc to ensure that the recommended procedures will not cause damage Kaba Ilco s standard warranty does not cover damages caused by installation Important The RAC 660G should always be installed in a secure...

Page 4: ...re Side Remote Unlock Fire Alarm Ingress Keypad RAC 660G PULL FIRE Request to Exit Power Adaptor Programming M Unit Locking Device Figure 2 2 2 1 Keypad readers Two types of keypads are available G Figure 3 Figure 4 G 3 x 4 Wall mount 2 x 6 Narrow Doorframe style 2 2 2 Controller box A Enclosure with cover metallic frame which contains the controller board Knockouts are available on 3 sides of the...

Page 5: ...x Philips wood screw 8 x 1 1 4 O 4x Nylon anchor 6 10 P 4x Concrete anchor 7 9 Q 1x Strain relief connector with locking nut R 1x Strain relief bushing S 2x Diode rectifier T 5x 8 steel flat washer U 3x Crimp terminal B connector Power Adaptor includes E 1x International 12 VDC output adaptor with integrated power cable and Interchangeable AC outlet prongs or F 1x North American 12 VDC output adap...

Page 6: ...ecklist and Exploded Views Continued 3 2 Exploded View Controller Box Hardware Bag Power Adaptor Peripherals Optional Devices 5x 4x 2x 4x 4x 1x 3x Figure 7 A B D Keypad Ingress G 2 x 6 or 3 x 4 H I K J F E International North American 1x T O S U Q R P N ...

Page 7: ...9 C The controller box must be in a location sheltered against exterior elements weather hazards and dripping water Do not use cord and wall outlets for mounting of the controller box The unit must be fixed with the hardware supplied Step 2 Identify location s for the keypad reader and required peripherals Important All peripherals used by any RAC 660G user must be placed at standard height prescr...

Page 8: ...ccess it is recommended to remove the access panel before installation If needed keep it nearby to refer to the wiring label or refer to Annex A at the end of this manual CAUTION Wire routing must be according to any local building codes or legislations 2 Two types of power adaptors are available dependant of the countries where controller box is to be installed E For international applications ma...

Page 9: ...red use the same connection instructions as indicated above 3 If a remote unlock button L is being used mount the button at the desired location and run a 2 conductor cable from the controller board B to the remote unlock button location Connect as per Annex A Table 1 NOTE Refer to manufactures wire gauge installation selections 4 Install a 2 conductor cable from the control panel to the location ...

Page 10: ...he controller box to help prevent the possibility of wire tampering or R Figure 12 E F NOTE The strain relief bushing R provided in the hardware bag has a movable attached plug When the plug is removed It leaves an opening that allows a double wire flat cable to be routed in Determine the routing needed for the wiring of the power adaptor E or F from AC power source to the controller box Remove th...

Page 11: ...st choose your door 5 Hold the PALM in close proximity to D12 located near SW2 and tap Program on the PALM When complete LED D41 should be on 5 3 Reset to Factory Default In the event the Door or Site ID of the premise is changed or a problem is suspected with the current configuration the 660G will reset to default 1 Note down the current DIP switch bank SW2 settings on the controller board C as ...

Page 12: ... Functionality 2 Remote Access Controller 660G Controller Board IMPORTANT Read manual before installation or maintenance of the unit G1 B I E F 124 511689 101 RD BLK Electric Strike 506381 Electromagnetic Lock 504631 NC C N O Normally Open REX Pushbar or Button Fire Alarm Panel Contact OPENS on fire alarm Not supplied by Kaba See NOTE K Bypass Active Reset SW1 SW2 D12 D44 D43 D42 D41 D45 D46 SW3 O...

Page 13: ... WIRE M Key Override J7 3 NO L Remote J8 1 REM UNL J7 4 GND Unlock J8 2 GND K REX J8 3 REX J8 4 GND Note Connections required are dependant on system options purchased Note Part numbers indicated subject to change Please refer to ordering guide for current numbering Table 1 Table 2 PCB Status LED s LED Description D46 Keypad RED LED D45 Keypad GREEN LED D41 Initialization D42 Not Used D43 Normal O...

Page 14: ...PK3512_09_07 REMOTE ACCESS CONTROLLER 660G 14 6 0 Annex B Drilling Template ...

Page 15: ...PK3512_09_07 REMOTE ACCESS CONTROLLER 660G 15 6 0 Annex B Drilling Template ...

Page 16: ...he 660G is programmed LED D41 should be on If not program it Re program the RAC 660G 1 Power Troubleshooting 2 Keypad Troubleshooting Symptom Action All controller board B LEDs are OFF Verify that the RAC 660G controller is connected properly to the power adaptor as per Annex A Table 1 Verify that AC power is active for the wall mount power adaptor If qualified with a multi meter verify that 12VDC...

Page 17: ... LED D47 is normally on and turns off when the Fire Alarm is present Verify that the 12V_Lock output of the RAC 660G controller is connected to the COMMON of the locking device relay Unit Resets when the relay activates If the diode is installed on the Electric strike as per Annex A to unlock the door verify the polarity of the diode Verify the wiring to the locking device 4 Locking Device Trouble...

Page 18: ...port 1 800 906 4526 Customer Service T 1 877 468 3555 F 514 735 6589 General Information www kabalodging com Online Consumable Orders www keycard com To access all of our easy steps please visit our Support Website http connect kabalodging com Printed in Canada PK3512_09_07 ...

Reviews: