Symptom  

Action

  Locking Device always unlocked 

-  If the Locking Device Relay LED (D31) on the RAC 660G controller is ON:

    

 

  •  Verify that the delay setting of the DIP switch (SW2) is correct.

    

 

  • Verify that the lock is in not Passage Mode.

   

 

-  If the Locking Device Relay LED (D31) on the RAC 660G controller is OFF:

    

 

  •  Verify that the Bypass switch is not active (Bypass LED, D21, is OFF).

    

 

  •  Verify that the Fire Alarm input not active (Input contact closed, Fire Alarm 

LED, D47, is ON).

    

 

  • Verify the wiring to the locking device.

  Locking device does not unlock 

- If the Locking Device Relay LED (D31) turns on:

    

 

  •  Verify that the Fire Alarm input is not active (Input contact closed, Fire 

Alarm LED, D47, is on).

    

 

  • Verify the wiring to the locking device.

   

 

-  If a diode is installed on the locking device, verify the polarity.

   

 

-  If the locking device Relay LED (D31) does not turn on:

    

 

   •  Verify that the Request to Exit or Remote Unlock activation unlocks the door.

    

 

   • Verify that the card is encoded properly.

    

 

   • Verify that the RAC 660G is not in Lockout mode.

    

 

  • Verify that the RAC 660G is programmed properly.

  Fire Alarm does not Unlock door 

-  Verify that the Fire Alarm input is connected to a Normally Closed contact.

   

 

-  Verify that the Fire Alarm LED (D47) is normally on and turns off when the 

Fire Alarm is present.

   

 

-  Verify that the 12V_Lock output of the RAC 660G controller is connected to 

the COMMON of the locking device relay. 

  Unit Resets when the relay activates 

-  If the diode is installed on the Electric strike as per Annex A,

  to unlock the door. 

   verify the polarity of the diode.

   

 

-  Verify the wiring to the locking device.

4. Locking Device Troubleshooting

5. Programming and Auditing Troubleshooting

 

Symptom  

Action

  Cannot program or audit the RAC 660G 

-  Verify that the RAC 660G controller is active: the Access (D43) LED should 

blink. If not, reset the RAC 660G Controller (press the Reset switch (SW1) or 
disconnect and reconnect the power).

   

 

-  Verify that the 660G enters programming mode when *,#,*,#, is pressed, or 

when a DIP switch (SW2) is toggled. The FUNC 1 LED (D45) blinks when the 
660G is in programming mode.

   

 

-  The 660G controller must still be in programming mode with LED (D45) 

blinking when the Program or Audit command is selected on the M-Unit.

   

 

-  Verify that the M-Unit is pointing toward the infrared Transceiver (D12) located 

beside the DIP switch (SW2) during programming and auditing. The distance 
between the M-Unit and the 660G controller should be a few inches (3 to 6 
inches).

   

 

-  If the RAC 660G is not initialized (Initialization LED, D41, is OFF)

   

 

-  If the RAC 660G was already initialized, it may need to be re-initialized: 

    

 

   •  Follow the instructions in section 5.3 “Reset to factory default”.

Summary of Contents for ILCO RAC 660G

Page 1: ...INSTALLATION GUIDE Remote Access Controller 660G PK3512 ...

Page 2: ...ntroller box 7 Step 2 Identify location s for the keypad reader and required peripherals 7 Step 3 Set the desired access delay 7 Step 4 Install strain relief 7 4 2 Installation Procedures 8 Step 5 Mounting the controller box 8 Step 6 Connect wiring 9 Step 7 Mounting wiring keypad reader 9 Step 8 Install strain relief bushing 10 Step 9 Completing the installation 10 5 0 Settings and Operation 11 5 ...

Page 3: ...0 906 4526 OR Visit the Kaba Support Website http connect kabalodging com Warnings and Cautions Please read and follow all directions carefully Important Carefully inspect windows doorframe door etc to ensure that the recommended procedures will not cause damage Kaba Ilco s standard warranty does not cover damages caused by installation Important The RAC 660G should always be installed in a secure...

Page 4: ...re Side Remote Unlock Fire Alarm Ingress Keypad RAC 660G PULL FIRE Request to Exit Power Adaptor Programming M Unit Locking Device Figure 2 2 2 1 Keypad readers Two types of keypads are available G Figure 3 Figure 4 G 3 x 4 Wall mount 2 x 6 Narrow Doorframe style 2 2 2 Controller box A Enclosure with cover metallic frame which contains the controller board Knockouts are available on 3 sides of the...

Page 5: ...x Philips wood screw 8 x 1 1 4 O 4x Nylon anchor 6 10 P 4x Concrete anchor 7 9 Q 1x Strain relief connector with locking nut R 1x Strain relief bushing S 2x Diode rectifier T 5x 8 steel flat washer U 3x Crimp terminal B connector Power Adaptor includes E 1x International 12 VDC output adaptor with integrated power cable and Interchangeable AC outlet prongs or F 1x North American 12 VDC output adap...

Page 6: ...ecklist and Exploded Views Continued 3 2 Exploded View Controller Box Hardware Bag Power Adaptor Peripherals Optional Devices 5x 4x 2x 4x 4x 1x 3x Figure 7 A B D Keypad Ingress G 2 x 6 or 3 x 4 H I K J F E International North American 1x T O S U Q R P N ...

Page 7: ...9 C The controller box must be in a location sheltered against exterior elements weather hazards and dripping water Do not use cord and wall outlets for mounting of the controller box The unit must be fixed with the hardware supplied Step 2 Identify location s for the keypad reader and required peripherals Important All peripherals used by any RAC 660G user must be placed at standard height prescr...

Page 8: ...ccess it is recommended to remove the access panel before installation If needed keep it nearby to refer to the wiring label or refer to Annex A at the end of this manual CAUTION Wire routing must be according to any local building codes or legislations 2 Two types of power adaptors are available dependant of the countries where controller box is to be installed E For international applications ma...

Page 9: ...red use the same connection instructions as indicated above 3 If a remote unlock button L is being used mount the button at the desired location and run a 2 conductor cable from the controller board B to the remote unlock button location Connect as per Annex A Table 1 NOTE Refer to manufactures wire gauge installation selections 4 Install a 2 conductor cable from the control panel to the location ...

Page 10: ...he controller box to help prevent the possibility of wire tampering or R Figure 12 E F NOTE The strain relief bushing R provided in the hardware bag has a movable attached plug When the plug is removed It leaves an opening that allows a double wire flat cable to be routed in Determine the routing needed for the wiring of the power adaptor E or F from AC power source to the controller box Remove th...

Page 11: ...st choose your door 5 Hold the PALM in close proximity to D12 located near SW2 and tap Program on the PALM When complete LED D41 should be on 5 3 Reset to Factory Default In the event the Door or Site ID of the premise is changed or a problem is suspected with the current configuration the 660G will reset to default 1 Note down the current DIP switch bank SW2 settings on the controller board C as ...

Page 12: ... Functionality 2 Remote Access Controller 660G Controller Board IMPORTANT Read manual before installation or maintenance of the unit G1 B I E F 124 511689 101 RD BLK Electric Strike 506381 Electromagnetic Lock 504631 NC C N O Normally Open REX Pushbar or Button Fire Alarm Panel Contact OPENS on fire alarm Not supplied by Kaba See NOTE K Bypass Active Reset SW1 SW2 D12 D44 D43 D42 D41 D45 D46 SW3 O...

Page 13: ... WIRE M Key Override J7 3 NO L Remote J8 1 REM UNL J7 4 GND Unlock J8 2 GND K REX J8 3 REX J8 4 GND Note Connections required are dependant on system options purchased Note Part numbers indicated subject to change Please refer to ordering guide for current numbering Table 1 Table 2 PCB Status LED s LED Description D46 Keypad RED LED D45 Keypad GREEN LED D41 Initialization D42 Not Used D43 Normal O...

Page 14: ...PK3512_09_07 REMOTE ACCESS CONTROLLER 660G 14 6 0 Annex B Drilling Template ...

Page 15: ...PK3512_09_07 REMOTE ACCESS CONTROLLER 660G 15 6 0 Annex B Drilling Template ...

Page 16: ...he 660G is programmed LED D41 should be on If not program it Re program the RAC 660G 1 Power Troubleshooting 2 Keypad Troubleshooting Symptom Action All controller board B LEDs are OFF Verify that the RAC 660G controller is connected properly to the power adaptor as per Annex A Table 1 Verify that AC power is active for the wall mount power adaptor If qualified with a multi meter verify that 12VDC...

Page 17: ... LED D47 is normally on and turns off when the Fire Alarm is present Verify that the 12V_Lock output of the RAC 660G controller is connected to the COMMON of the locking device relay Unit Resets when the relay activates If the diode is installed on the Electric strike as per Annex A to unlock the door verify the polarity of the diode Verify the wiring to the locking device 4 Locking Device Trouble...

Page 18: ...port 1 800 906 4526 Customer Service T 1 877 468 3555 F 514 735 6589 General Information www kabalodging com Online Consumable Orders www keycard com To access all of our easy steps please visit our Support Website http connect kabalodging com Printed in Canada PK3512_09_07 ...