Kaba ILCO RAC 660G Installation Manual Download Page 11

PK3512_09_07 • REMOTE ACCESS CONTROLLER - 660G

11

5.1 Testing

1.    If not already done, connect the AC power adaptor, and / or 

turn on the AC current.

2.    Verify that the Power Status LED on the panel is On.
3.     Verify that the D43 LED on the controller board (C) blink 

continuously.

4.     Activate the Bypass switch, SW3 on the controller board (C).
5.    Verify that the locking device is activated. 

NOTE: 

 If the locking device is not activated, verify that the Fire 
Alarm input is properly connected, or a jumper wire is 
connected.

6.    De-activate  the  bypass  switch,  SW3  on  the  controller 

board (C).

7. 

 To test the kaypad reader enter a valid code. Verify that 
the door unlocks. The unlock time will correspond to the delay 
set by the DIP switches as per Annex A, Table 4.

8.    If a REX button is connected, press it and verify that the 

door unlocks.

9.    If  a  Remote  Unlock  button  is  connected,  press  it  and 

verify that the door unlocks.

10.     If  the  660G  is  connected  to  a  fire  panel  and  the 

electromagnetic lock powered by the 12 VDC output of 
the 660G, verify that the electromagnetic lock or a fail-
safe electric strike is deactivated when the fire alarm is 
active (open input).

11.    The 660G is now ready to be Programmed.

5.2 Programming using an M-Unit

The controller can be programmed directly on the PCB via a 
PALM. 

Steps to program the RAC with PALM:

1.    For  step  by  step  programming  instructions,  refer  to 

www.kaba-ecode.com  on  line  help  getting  started  and 
maintenance unit.

2. 

 Set the dip switch SW2 bank (OFF,OFF,OFF,OFF) refer to 
Access Delay Table SW2, Table 3, Annex A.

3. 

 Toggle  any  one  of  the  Four  SW2  switches  to  ON.  LED 
D45  should  blink  to  indicate  that  the  660G  is  ready  to 
communicate, LED D41 should be on.

4. 

 On  the  PALM  open  the  Oracode  application  software, 
select Door List, choose your door.

5. 

 Hold  the  PALM  in  close  proximity  to  D12  located  near 
SW2 and tap “Program” on the PALM. When complete 
LED D41 should be on.

5.3 Reset to Factory Default

In the event the Door or Site ID of the premise is changed or a 
problem is suspected with the current configuration, the 660G 
will reset to default.
1.     Note down the current DIP switch bank SW2 settings on 

the controller board (C) as this is the current delay setting 
for the peripherals used.

2.     Set  the  switches  on  DIP  switch  bank  SW2  on  the 

controller board (C) to CFG #16 (OFF, OFF, OFF, OFF) as 
per Annex A, Table 4.

3.    Verify that the initialization LED (D41) is OFF.
4.     660G is ready to be programmed. Refer to steps How to 

program the RAC 5.2.

5.     Set the DIP switch positions back to the chosen access 

delay settings as noted above, or reset based on values 
shown in Annex A, Table 3.

5.4 Power Failure

In the event of an electrical failure, the system will recover 
automatically and should require no additional programming if 
the electrical power is restored within 3 days.

When electrical power is restored after a power failure, verify 
that  a  valid  code  is  accepted  normally  with  a  single  flash  of 
the green LED on the keypad. If the green LED blinks twice, or 
if the code is refused, the 660G needs to be re-programmed 
(See section 5.2).

5.5 Loading Recommendations

CAUTION: Do not exceed the load limitations  
of the control panel.

!

The maximum recommended load for all output relays in the 
keypad reader control panel is 1 Amp at 30 VDC. The current 
supplied by the controller board (B) for the locking device used 
is  0.75  Amps  from  connector  J18,  pin  1.  Refer  to  Annex  A, 
Table 1.

5.6 System Deactivation

In order to deactivate the keypad reader control panel, disconnect 
the AC power either by removing the power adaptor from the wall 
outlet, or by shutting off the main breaker switch for the AC line 
to the wall outlet the control panel is connected to.

5.0  Setting and Operation

Summary of Contents for ILCO RAC 660G

Page 1: ...INSTALLATION GUIDE Remote Access Controller 660G PK3512 ...

Page 2: ...ntroller box 7 Step 2 Identify location s for the keypad reader and required peripherals 7 Step 3 Set the desired access delay 7 Step 4 Install strain relief 7 4 2 Installation Procedures 8 Step 5 Mounting the controller box 8 Step 6 Connect wiring 9 Step 7 Mounting wiring keypad reader 9 Step 8 Install strain relief bushing 10 Step 9 Completing the installation 10 5 0 Settings and Operation 11 5 ...

Page 3: ...0 906 4526 OR Visit the Kaba Support Website http connect kabalodging com Warnings and Cautions Please read and follow all directions carefully Important Carefully inspect windows doorframe door etc to ensure that the recommended procedures will not cause damage Kaba Ilco s standard warranty does not cover damages caused by installation Important The RAC 660G should always be installed in a secure...

Page 4: ...re Side Remote Unlock Fire Alarm Ingress Keypad RAC 660G PULL FIRE Request to Exit Power Adaptor Programming M Unit Locking Device Figure 2 2 2 1 Keypad readers Two types of keypads are available G Figure 3 Figure 4 G 3 x 4 Wall mount 2 x 6 Narrow Doorframe style 2 2 2 Controller box A Enclosure with cover metallic frame which contains the controller board Knockouts are available on 3 sides of the...

Page 5: ...x Philips wood screw 8 x 1 1 4 O 4x Nylon anchor 6 10 P 4x Concrete anchor 7 9 Q 1x Strain relief connector with locking nut R 1x Strain relief bushing S 2x Diode rectifier T 5x 8 steel flat washer U 3x Crimp terminal B connector Power Adaptor includes E 1x International 12 VDC output adaptor with integrated power cable and Interchangeable AC outlet prongs or F 1x North American 12 VDC output adap...

Page 6: ...ecklist and Exploded Views Continued 3 2 Exploded View Controller Box Hardware Bag Power Adaptor Peripherals Optional Devices 5x 4x 2x 4x 4x 1x 3x Figure 7 A B D Keypad Ingress G 2 x 6 or 3 x 4 H I K J F E International North American 1x T O S U Q R P N ...

Page 7: ...9 C The controller box must be in a location sheltered against exterior elements weather hazards and dripping water Do not use cord and wall outlets for mounting of the controller box The unit must be fixed with the hardware supplied Step 2 Identify location s for the keypad reader and required peripherals Important All peripherals used by any RAC 660G user must be placed at standard height prescr...

Page 8: ...ccess it is recommended to remove the access panel before installation If needed keep it nearby to refer to the wiring label or refer to Annex A at the end of this manual CAUTION Wire routing must be according to any local building codes or legislations 2 Two types of power adaptors are available dependant of the countries where controller box is to be installed E For international applications ma...

Page 9: ...red use the same connection instructions as indicated above 3 If a remote unlock button L is being used mount the button at the desired location and run a 2 conductor cable from the controller board B to the remote unlock button location Connect as per Annex A Table 1 NOTE Refer to manufactures wire gauge installation selections 4 Install a 2 conductor cable from the control panel to the location ...

Page 10: ...he controller box to help prevent the possibility of wire tampering or R Figure 12 E F NOTE The strain relief bushing R provided in the hardware bag has a movable attached plug When the plug is removed It leaves an opening that allows a double wire flat cable to be routed in Determine the routing needed for the wiring of the power adaptor E or F from AC power source to the controller box Remove th...

Page 11: ...st choose your door 5 Hold the PALM in close proximity to D12 located near SW2 and tap Program on the PALM When complete LED D41 should be on 5 3 Reset to Factory Default In the event the Door or Site ID of the premise is changed or a problem is suspected with the current configuration the 660G will reset to default 1 Note down the current DIP switch bank SW2 settings on the controller board C as ...

Page 12: ... Functionality 2 Remote Access Controller 660G Controller Board IMPORTANT Read manual before installation or maintenance of the unit G1 B I E F 124 511689 101 RD BLK Electric Strike 506381 Electromagnetic Lock 504631 NC C N O Normally Open REX Pushbar or Button Fire Alarm Panel Contact OPENS on fire alarm Not supplied by Kaba See NOTE K Bypass Active Reset SW1 SW2 D12 D44 D43 D42 D41 D45 D46 SW3 O...

Page 13: ... WIRE M Key Override J7 3 NO L Remote J8 1 REM UNL J7 4 GND Unlock J8 2 GND K REX J8 3 REX J8 4 GND Note Connections required are dependant on system options purchased Note Part numbers indicated subject to change Please refer to ordering guide for current numbering Table 1 Table 2 PCB Status LED s LED Description D46 Keypad RED LED D45 Keypad GREEN LED D41 Initialization D42 Not Used D43 Normal O...

Page 14: ...PK3512_09_07 REMOTE ACCESS CONTROLLER 660G 14 6 0 Annex B Drilling Template ...

Page 15: ...PK3512_09_07 REMOTE ACCESS CONTROLLER 660G 15 6 0 Annex B Drilling Template ...

Page 16: ...he 660G is programmed LED D41 should be on If not program it Re program the RAC 660G 1 Power Troubleshooting 2 Keypad Troubleshooting Symptom Action All controller board B LEDs are OFF Verify that the RAC 660G controller is connected properly to the power adaptor as per Annex A Table 1 Verify that AC power is active for the wall mount power adaptor If qualified with a multi meter verify that 12VDC...

Page 17: ... LED D47 is normally on and turns off when the Fire Alarm is present Verify that the 12V_Lock output of the RAC 660G controller is connected to the COMMON of the locking device relay Unit Resets when the relay activates If the diode is installed on the Electric strike as per Annex A to unlock the door verify the polarity of the diode Verify the wiring to the locking device 4 Locking Device Trouble...

Page 18: ...port 1 800 906 4526 Customer Service T 1 877 468 3555 F 514 735 6589 General Information www kabalodging com Online Consumable Orders www keycard com To access all of our easy steps please visit our Support Website http connect kabalodging com Printed in Canada PK3512_09_07 ...

Reviews: