Https://www.bueno-electric.com
BUENO ELECTRIC
BUENO ELECTRIC
BUENO ELECTRIC
BUENO ELECTRIC
Contact: [email protected]
Fax: +86-25-51816989
20
Ser.No
Setting name
Range
Unit
Remarks
35
Long startup current
settings
0.2
~
100.0
A
36
Permit start time
0.1
~
100.0
s
37
F-C blocking current
0.2
~
100.0
A
38
F—C Tripped over time
0.04
~
20.00
s
39
Non-electric quantity 1
time delay
0
~
6000
s
40
Non-electric quantity 2
time delay
0
~
6000
s
41
Non-electric quantity 3
time delay
0
~
6000
s
42
Measure TA ratio
(
kA/A
)
0.01
~
10
primary measureTA ratio/1000
43
TV ratio
(
kV/V
)
0.01
~
10
primary TV ratio/1000
Control character 1
(
KG1
)
definitions
of BEPR- 822U Digital Motor
Comprehensive
Control character 1
(
KG1
)
definitions of BEPR- 822U Digital Motor Comprehensive Protection
Bit
Meanings for 1
Meanings for 0
15
TA rated current is
1A.
TA rated current is
5A.
14
Zero-sequence over-voltage
trip
Zero-sequence over-voltage
alarm
13
Over-voltage
trip
Over-voltage
alarm
12
Control back to break the discriminant investment
Control back to break the discriminant exit
11
Three phase protection TA
Two phase protection TA
10
2X 13214 switch on 3I0
∶
2X 13214
∶
switch on Ibc
9
4 X: 3 control voltage protection
4 X: 3 for Non-electric input
8
Non-electric quantity 2
exits
Non-electric quantity 2
operates
7
Non-electric quantity 1
exits
Non-electric quantity 1
operates
6
Long startup protection
operates
Long startup protection
exits
5
Overload
trip
Overload
alarm