KG2
)
definition of BEPR- 822U Digital Motor Comprehensive Protection
Specifications:
1) DI terminals in BEPR- 822U 4X:1, 4X:2, 4X:4 and 4X:8
,
when their corresponding functions set in
KG1, KG2 exit, could be used as ordinary switching input terminals.
2) The non-electric quantity protections in BEPR- 822U are defined as follows.
According to different project terminals, related changes must be made.
4
Zero-sequence over-current
trip
Zero-sequence over-current
alarm
3
Negative-sequence zone I selects
inverse-time limit mode
Negative-sequence zone I selects
definite-time limit mode
2
Over-current selects inverse-time limit mode
Over-current selects definite-time limit
mode
1
Overheat blocking
operates
Overheat blocking
exits
0
Overheat alarm
operates
Overheat alarm
exits
Bit
Meanings for 1
Meanings for 0
15
Motor startup discrimination exits
Motor startup discrimination operates.
14
~
13
Standby
Standby
12
Measuring CT: Three-phase
Measuring CT:
T
wo-phase
11
External thermal return - operates
External thermal return - exits
10
3U0 external PT
3U0 from itself
9
FC large current blocking operates
FC large current blocking exits.
8
Rotor-locked protection operates
Rotor-locked protection exits.
7
Fuse protection trip
Fuse protection alarm
6
X5
∶
122are used as pulses
X5
∶
122 are used as telesignal variables
5
Fuse protection operates
Fuse protection exits
4
4X:4 external thermal reset operates
4X 4
∶
external thermal reset exits
3
4X 8
∶
external reset
operates
4X 8
∶
external reset
exits
2
Standby
Standby
1
TV wire break discrimination
operates
TV wire break discrimination
exits.
0
Standby
Standby