18
1) “ Measure Ia”
,
“Measure Ic” display the rms of the measuring current transformer phase A and phase C
current. If there is no phase B measurement, 0 is displayed “Measure Ib”.
2) Measurement Uab
,
Ubc
,
Uca have the same input terminal as protection voltage Uab
,
Ubc
,
Uca. However
the data are directly taken from special measurement module. “cosΦ” is power factor
3) Active power P is directly taken from special measurement module.
4.18.3 Power measurement
This device applies two-meter-method to measure power. The direction of reactive power Q is decided by
corresponding angle of protection line voltage and current.
Therefore, when examining reactive power, phase A and phase C protection current must be connected
simultaneously.
5 Settings and Setting Specifications
5.1 Setting value list and specifications of BEPR- 822U Digital Asynchronous Motor Protection
Setting value list of BEPR- 822U Digital Motor Comprehensive Protection
Ser.No
Setting name
Range
Unit
Remarks
1
Control character 1
0000
~
FFFF
No
Refer to definition of control
character
1(KG1)
2
Control character 2
0000
~
FFFF
No
Refer to definition of control
character
2(KG2)
3
Motor rated current
0.2
~
20.0
A
I
e
4
Motor startup time
0.0
~
60
s
T
start0
5
Instantaneous current setting
0.2
~
100.0
A
6
Instantaneous time
0.0
~
20.00
s
7
Over-current settings
0.2
~
100.0
A
8
Over-current time
0.1
~
3000
s
9
Over-current
inverse-time
limit time
0.1
~
3000
s
10
Zero-sequence 1 current
0.02
~
5.50
A
11
Zero-sequence current 1
time
0.0
~
20.00
s
12
Zero-sequence 2 current
0.1
~
20.00
A
13
Zero-sequence current 2 time
0.0
~
20.00
s
14
Negative-sequence zone I 0.1
~
100.0
A