11.28 RELAY PROGRAMMING
All relays can be set to any of the available functions (user assignable), all
relay functions are selectable from a drop down list for each of the three
relays outputs.
11.29 RELAY FUNCTIONS
The following table is for use for the relay programming options.
Mode
Trigger Condition
Zone 1 Alarm
Triggers when Zone 1 is armed AND
Any Zone 1 alarm occurs, these include:
• The Fence Voltage has fallen below the Fence
Voltage Alarm Level (Low Voltage)
• The Feed Current has increased above the Feed
Current Alarm Level (Short)
• Anti-bridging
• Energizer failure
• Fence Cut alarm
Zone 1 Alarm or
Disarmed
Triggers when Zone 1 is disarmed OR
Any Zone 1 alarm occurs, these include:
• The Fence Voltage has fallen below the Fence
Voltage Alarm Level (Low Voltage)
• The Feed Current has increased above the Feed
Current Alarm Level (Short)
• Anti-bridging
• Energizer failure
• Fence Cut alarm
Zone 1 Armed
Zone 1 is Armed