11.7 PULSE TIME
Sets the period between energizer pulses.
Range 1.0 second to 2.0 seconds. Default 1.3 seconds
Virtual Keypad:
Enter the
Configuration
page and adjust
Pulse Time
ac
-
cordingly. Click
Save Settings.
11.8 FENCE CUT ALARM
JMBx-ZM50 only
Sets the percentage balance change to either side of 50% for which the
Fence Cut alarm will occur. In normal running, with no faults, the fence
currents should be well balanced. Meaning the current Feed 1 and Feed 2
will be close to the same value in Amps. When they are equal the balance
value is close to 50%.
If the fence is cut the currents will be unbalanced. A setting of 20 means
that the Fence Cut alarm will show if the balance moves below 30% or
above 70%.
A Fence Short alarm will take precedence over a Cut alarm.
On some fences a fence load device may need to be installed to ensure this
alarm worked properly for all fence cuts.
Range 0% to 50%. Default 20%
Virtual Keypad:
Enter the
Configuration
page and alter the
Cut Alarm
val
-
ue. Click
Save Settings.
11.9 FENCE VOLTAGE ALARM LEVEL (ZONE 1)
Sets the alarm threshold for a Fence Alarm. If the fence voltage decreases
below this threshold for more than the Fence Alarm Delay a fence alarm
will occur.
A Fence Short alarm takes precedence over this alarm.