Table 11: SRX100 Services Gateway Specifications
(continued)
Value
Specification
Normal operation ensured in temperature range of 32°F
(0°C) to 104°F (+40°C)
Nonoperating storage temperature in shipping container:
–40°F (–40°C) to 158°F (70°C)
NOTE:
The SRX100 Services Gateway operating
temperature is 35°C when installed in a rack.
Temperature
The maximum thermal values for the two models of services
gateways are as follows:
•
Low Memory — AC power: 80 BTU/hour (21.5 W)
•
High Memory — AC power: 80 BTU/hour (21.5 W)
NOTE:
These specifications are estimates and subject to
change.
Maximum thermal output
Figure 5: SRX100 Services Gateway
CAUTION:
Before removing or installing components of a functioning services
gateway, attach an electrostatic discharge (ESD) strap to an ESD point and
place the other end of the strap around your bare wrist. Failure to use an ESD
strap could result in damage to the services gateway.
Related
Documentation
SRX100 Services Gateway Description on page 3
•
•
SRX100 Services Gateway Front Panel and Back Panel Views on page 13
•
Monitoring the SRX100 Services Gateway Components Using LEDs on page 97
•
SRX100 Services Gateway Electrical Safety Guidelines and Warnings on page 141
SRX100 Services Gateway Cabinet Requirements
The SRX100 Services Gateway can be installed in a standard 31.5 in. (800 mm) or larger
enclosed cabinet.
Table 12 on page 26
provides the details on cabinet size, clearance,
and airflow requirements.
25
Copyright © 2015, Juniper Networks, Inc.
Chapter 4: Planning and Preparing the Site