Jung FM ST 50 UP Operating Instructions Manual Download Page 8

Dimming adjustment time

1…60 s
Basic setting: 4 s

Time from minimum
brightness until reaching
maximum brightness (dimming
speed).

Run-on time

0 s … 24 h
Basic setting: 0 s

As soon as a run-on time has
been entered, the actuator will
no longer remain on
permanently, but only for the
length of the run-on time. The
run-on time is restarted if
actuation is repeated. This
parameter is directly
connected to the "Manual
switch-off of run-on time"
parameter.
Note: The set time apply to
operation using radio
transmitters. The device is
switched immediately when
the 

Prog

 button is pressed.

Behaviour after the end of the
disabling function

On
Off
no change
Last value
Basic setting: No change

Behaviour of the output when
a block is removed.

Behaviour on voltage return

On
Off
Last value
Configured brightness
Basic setting: Off

Defines the behaviour of the
output after voltage return.

Brightness on voltage return

0...100 %
Basic setting: 100 %

Brightness value, set by the
output after voltage return
(mains voltage). The
parameter "Behaviour after
voltage return" must be set to
"Configured brightness".
Note: If the value is above the
set maximum brightness or
below the minimum
brightness, then the system
will switch to the appropriate
limit value.

8/11

82581013
J:0082581013

13.03.2014

eNet

Radio push-button controller 1-10 V

Summary of Contents for FM ST 50 UP

Page 1: ... part of the product and must remain with the end customer 2 Device components Figure 1 Device components 1 Operating mode switch 2 Button Prog 3 Status LED 4 Measuring points for voltage measurement terminals rear mounted 3 Function System information This device is a part of the eNet system High transmission reliability at a radio frequency of 868 MHz is achieved by the transmission behaviour an...

Page 2: ...d signalling could vary from what is described here i The parameter list is in the Internet in the documentation for this device Supplementary functions with eNet server Update of the device software Repeater function Reading of error memory Response after mains voltage return The response after mains voltage return can be configured with the eNet server Default setting Off 4 Operation Operation w...

Page 3: ...ous voltages to the device or load couple the miniature circuit breakers or label them with a warning to ensure disconnection is guaranteed o Insert the actuator in the appliance box in such a way that the Prog button 2 and status LED 3 are visible Figure 3 Operating mode switch Position Description PC Operating mode parameter set with eNet server G 1 10 V operation min Setting of the minimum brig...

Page 4: ...r The actuator and radio transmitter exit the programming mode automatically i If the status LED of the control unit flashes 3 times at 1 second intervals for approx 5 seconds then the programming operation was not successful All the memory locations in the actuator or radio transmitter are occupied i All On and All Off buttons of a radio transmitter are connected to the actuator automatically as ...

Page 5: ...onger than 4 seconds The light switches off briefly and then switches on again to the new switch on brightness Switch on brightness is saved i Alternatively the switch on brightness can be saved with a radio transmitter e g wall transmitter 6 Appendix The icon confirms the conformity of the product to the relevant guidelines 6 1 Technical data Rated voltage AC 230 V Mains frequency 50 60 Hz Standb...

Page 6: ...ory setting Operating mode Normal operation Continuous on Continuous off Basic setting Normal Operation Normal operation The output can be operated with radio transmitters and the Prog button Continuous on The output switches to continuously On All operations of radio transmitters and the Prog button are ignored Continuous off The output switches to continuously Off All operations of radio transmi...

Page 7: ...as not yet been switched off due to the delay when a switch on command comes then the load will remain on Note The set time apply to operation using radio transmitters The device is switched immediately when the Prog button is pressed Dim up ramp 0 s 24 h Basic setting 0 s Time between switch on and reaching switch on brightness The light is switched on at minimum brightness and then dimmed to the...

Page 8: ...e Prog button is pressed Behaviour after the end of the disabling function On Off no change Last value Basic setting No change Behaviour of the output when a block is removed Behaviour on voltage return On Off Last value Configured brightness Basic setting Off Defines the behaviour of the output after voltage return Brightness on voltage return 0 100 Basic setting 100 Brightness value set by the o...

Page 9: ...is the highest priority and 4 the lowest 0 means no priority Priority restraint 0 4 Basic setting 2 Specifies the priority for recalling and removing a scene of type Forced position for the channel Priority wind alarm 0 4 Basic setting 3 Specifies the priority for recalling and removing a scene of type Wind alarm for the channel Priority sun protection 0 4 Basic setting 0 Specifies the priority fo...

Page 10: ... level higher than the maximum brightness then the system will dim to maximum brightness Hotel function On Off Basic setting Off If the hotel function is activated the system will dim to 20 brightness when a switch off command is made Switch off is only possible with a forced position command Note If the minimum brightness is set to greater than 20 then the system dims to the set minimum brightnes...

Page 11: ...t polarity Cause 2 1 10 V control cables have short circuited Eliminate short circuit Lamps switch to maximum brightness No dimming is possible Cause 1 10 V control cables are interrupted or not connected Connect the control cables correctly 6 4 Accessories Installation box Art No FM EBG eNet server Art No ENET SERVER 6 5 Warranty We reserve the right to make technical and formal changes to the pr...

Reviews: