Current dimming value
The load can be dimmed using the slider or a
brightness value entry.
Load state
The load can be switched on or off.
Restraint
Display of forced position status.
Switching cycle counter
Display of the switching cycles with the factor
10, e.g. the value 5 x 10 is displayed for 50
switching cycles.
Total operating hours
Display of the operating hours since the start
of operation.
Operating hours
Display of the operating hours since the last
restart in the Settings window.
6.3 Troubleshooting
Lamps switch to minimum brightness. No dimming is possible.
Cause 1: 1-10 V interface is connected in reverse polarity.
Connect the control cables with the correct polarity.
Cause 2: 1-10 V control cables have short-circuited.
Eliminate short-circuit.
Lamps switch to maximum brightness. No dimming is possible.
Cause: 1-10 V control cables are interrupted or not connected.
Connect the control cables correctly.