Jung FM ST 50 UP Operating Instructions Manual Download Page 5

o

Press the 

Prog

 button for at least 20 seconds.

The status LED flashes after 4 seconds. After 20 seconds the status LED flashes faster.

o

Release 

Prog

 button and press briefly once again within 10 seconds.

The status LED flashes more slowly for approx. 5 seconds.
The actuator is reset to default setting.

Setting the minimum brightness

The minimum brightness can be set within a range of approx. 1...67 %, if, e.g. the light flickers
at low brightness or to compensate for differences in brightness.

o

Turn operating mode switch (1) to the 

min.

 position.

o

Adjust brightness with the radio transmitter.

o

Turn operating mode switch to the original position again.
When leaving the position 

min.

, the minimum brightness is saved.

Save switch-on brightness

o

Switch on light.

o

Adjust brightness with the radio transmitter.

o

Press button 

Prog

 (2) for longer than 4 seconds.

The light switches off briefly and then switches on again to the new switch-on brightness. 
Switch-on brightness is saved.

i

Alternatively, the switch-on brightness can be saved with a radio transmitter, e.g. wall
transmitter.

6 Appendix

The icon confirms the conformity of the product to the relevant guidelines.

6.1 Technical data

Rated voltage

AC 230 V ~

Mains frequency

50 / 60 Hz

Standby power

max. 0.5 W

Ambient temperature

-25 ... +70 °C

Contact type

µ

Control voltage

0.5 ... 11 V

Control current

max. 50 mA

Switching current
Ohmic

6 A

Fluorescent lamps

3 AX

Minimum switching current

100 mA

Connected load
Ohmic load

1380 W

Capacitive load

690 VA (560 µF)

Connection
single stranded

0.75 ... 4 mm²

Finely stranded with conductor sleeve

0.75 ... 2.5 mm²

Dimensions Ø×H

53×28 mm

Total length power cable

max. 100 m

Total length of control cable

max. 100 m

Radio frequency

868.3 MHz

Transmitting power

max. 20 mW

Transmitting range in free field

typical 100 m

5/11

82581013
J:0082581013

13.03.2014

eNet

Radio push-button controller 1-10 V

Summary of Contents for FM ST 50 UP

Page 1: ... part of the product and must remain with the end customer 2 Device components Figure 1 Device components 1 Operating mode switch 2 Button Prog 3 Status LED 4 Measuring points for voltage measurement terminals rear mounted 3 Function System information This device is a part of the eNet system High transmission reliability at a radio frequency of 868 MHz is achieved by the transmission behaviour an...

Page 2: ...d signalling could vary from what is described here i The parameter list is in the Internet in the documentation for this device Supplementary functions with eNet server Update of the device software Repeater function Reading of error memory Response after mains voltage return The response after mains voltage return can be configured with the eNet server Default setting Off 4 Operation Operation w...

Page 3: ...ous voltages to the device or load couple the miniature circuit breakers or label them with a warning to ensure disconnection is guaranteed o Insert the actuator in the appliance box in such a way that the Prog button 2 and status LED 3 are visible Figure 3 Operating mode switch Position Description PC Operating mode parameter set with eNet server G 1 10 V operation min Setting of the minimum brig...

Page 4: ...r The actuator and radio transmitter exit the programming mode automatically i If the status LED of the control unit flashes 3 times at 1 second intervals for approx 5 seconds then the programming operation was not successful All the memory locations in the actuator or radio transmitter are occupied i All On and All Off buttons of a radio transmitter are connected to the actuator automatically as ...

Page 5: ...onger than 4 seconds The light switches off briefly and then switches on again to the new switch on brightness Switch on brightness is saved i Alternatively the switch on brightness can be saved with a radio transmitter e g wall transmitter 6 Appendix The icon confirms the conformity of the product to the relevant guidelines 6 1 Technical data Rated voltage AC 230 V Mains frequency 50 60 Hz Standb...

Page 6: ...ory setting Operating mode Normal operation Continuous on Continuous off Basic setting Normal Operation Normal operation The output can be operated with radio transmitters and the Prog button Continuous on The output switches to continuously On All operations of radio transmitters and the Prog button are ignored Continuous off The output switches to continuously Off All operations of radio transmi...

Page 7: ...as not yet been switched off due to the delay when a switch on command comes then the load will remain on Note The set time apply to operation using radio transmitters The device is switched immediately when the Prog button is pressed Dim up ramp 0 s 24 h Basic setting 0 s Time between switch on and reaching switch on brightness The light is switched on at minimum brightness and then dimmed to the...

Page 8: ...e Prog button is pressed Behaviour after the end of the disabling function On Off no change Last value Basic setting No change Behaviour of the output when a block is removed Behaviour on voltage return On Off Last value Configured brightness Basic setting Off Defines the behaviour of the output after voltage return Brightness on voltage return 0 100 Basic setting 100 Brightness value set by the o...

Page 9: ...is the highest priority and 4 the lowest 0 means no priority Priority restraint 0 4 Basic setting 2 Specifies the priority for recalling and removing a scene of type Forced position for the channel Priority wind alarm 0 4 Basic setting 3 Specifies the priority for recalling and removing a scene of type Wind alarm for the channel Priority sun protection 0 4 Basic setting 0 Specifies the priority fo...

Page 10: ... level higher than the maximum brightness then the system will dim to maximum brightness Hotel function On Off Basic setting Off If the hotel function is activated the system will dim to 20 brightness when a switch off command is made Switch off is only possible with a forced position command Note If the minimum brightness is set to greater than 20 then the system dims to the set minimum brightnes...

Page 11: ...t polarity Cause 2 1 10 V control cables have short circuited Eliminate short circuit Lamps switch to maximum brightness No dimming is possible Cause 1 10 V control cables are interrupted or not connected Connect the control cables correctly 6 4 Accessories Installation box Art No FM EBG eNet server Art No ENET SERVER 6 5 Warranty We reserve the right to make technical and formal changes to the pr...