Intended use

-

Switching and brightness setting of luminaires with 1-10 V interface

-

Operation with suitable radio transmitters

-

Mounting in appliance box according to DIN 49073 in combination with a suitable cover.

-

Installation in surface-mounted housing or panel-mounted housing (accessories) for
suspended ceilings

Product characteristics

-

Switch-on brightness can be saved permanently

-

Minimum brightness can be saved permanently

-

Scene operation possible

-

Status indicator of the 1-10 V subscribers via LED

-

Status feedback to radio transmitter

-

1-10 V subscribers switchable with 

Prog

 button

-

1-10 V interface is protected against reverse polarity 

Can be set with eNet server:
-

Maximum brightness

-

Dimming speed

-

Switch-on delay / switch-off delay

-

Dim up/dim down ramp

-

Switch-off warning

-

Operation locks

-

Continuous on, Continuous off

-

Hotel function

-

Run-on time

-

Light control

i

If settings are changed with the eNet server, operation and signalling could vary from what
is described here.

i

The parameter list is in the Internet in the documentation for this device.

Supplementary functions with eNet server: 
-

Update of the device software

-

Repeater function

-

Reading of error memory

Response after mains voltage return

The response after mains voltage return can be configured with the eNet server. Default setting:
Off.

4 Operation

Operation with radio transmitters

Operation is with radio transmitters, please observe the radio transmitter instructions.

5 Information for electrically skilled persons

5.1 Fitting and electrical connection

DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before carrying out work on the device or load, disengage all the
corresponding circuit breakers. Cover up live parts in the working environment.

Mounting and connecting actuator

To ensure good transmission quality, keep a sufficient distance from any possible sources of
interference, e.g. metallic surfaces, microwave ovens, hi-fi and TV systems, ballasts or
transformers. 

2/11

82581013
J:0082581013

13.03.2014

eNet

Radio push-button controller 1-10 V

Summary of Contents for FM ST 50 UP

Page 1: ... part of the product and must remain with the end customer 2 Device components Figure 1 Device components 1 Operating mode switch 2 Button Prog 3 Status LED 4 Measuring points for voltage measurement terminals rear mounted 3 Function System information This device is a part of the eNet system High transmission reliability at a radio frequency of 868 MHz is achieved by the transmission behaviour an...

Page 2: ...d signalling could vary from what is described here i The parameter list is in the Internet in the documentation for this device Supplementary functions with eNet server Update of the device software Repeater function Reading of error memory Response after mains voltage return The response after mains voltage return can be configured with the eNet server Default setting Off 4 Operation Operation w...

Page 3: ...ous voltages to the device or load couple the miniature circuit breakers or label them with a warning to ensure disconnection is guaranteed o Insert the actuator in the appliance box in such a way that the Prog button 2 and status LED 3 are visible Figure 3 Operating mode switch Position Description PC Operating mode parameter set with eNet server G 1 10 V operation min Setting of the minimum brig...

Page 4: ...r The actuator and radio transmitter exit the programming mode automatically i If the status LED of the control unit flashes 3 times at 1 second intervals for approx 5 seconds then the programming operation was not successful All the memory locations in the actuator or radio transmitter are occupied i All On and All Off buttons of a radio transmitter are connected to the actuator automatically as ...

Page 5: ...onger than 4 seconds The light switches off briefly and then switches on again to the new switch on brightness Switch on brightness is saved i Alternatively the switch on brightness can be saved with a radio transmitter e g wall transmitter 6 Appendix The icon confirms the conformity of the product to the relevant guidelines 6 1 Technical data Rated voltage AC 230 V Mains frequency 50 60 Hz Standb...

Page 6: ...ory setting Operating mode Normal operation Continuous on Continuous off Basic setting Normal Operation Normal operation The output can be operated with radio transmitters and the Prog button Continuous on The output switches to continuously On All operations of radio transmitters and the Prog button are ignored Continuous off The output switches to continuously Off All operations of radio transmi...

Page 7: ...as not yet been switched off due to the delay when a switch on command comes then the load will remain on Note The set time apply to operation using radio transmitters The device is switched immediately when the Prog button is pressed Dim up ramp 0 s 24 h Basic setting 0 s Time between switch on and reaching switch on brightness The light is switched on at minimum brightness and then dimmed to the...

Page 8: ...e Prog button is pressed Behaviour after the end of the disabling function On Off no change Last value Basic setting No change Behaviour of the output when a block is removed Behaviour on voltage return On Off Last value Configured brightness Basic setting Off Defines the behaviour of the output after voltage return Brightness on voltage return 0 100 Basic setting 100 Brightness value set by the o...

Page 9: ...is the highest priority and 4 the lowest 0 means no priority Priority restraint 0 4 Basic setting 2 Specifies the priority for recalling and removing a scene of type Forced position for the channel Priority wind alarm 0 4 Basic setting 3 Specifies the priority for recalling and removing a scene of type Wind alarm for the channel Priority sun protection 0 4 Basic setting 0 Specifies the priority fo...

Page 10: ... level higher than the maximum brightness then the system will dim to maximum brightness Hotel function On Off Basic setting Off If the hotel function is activated the system will dim to 20 brightness when a switch off command is made Switch off is only possible with a forced position command Note If the minimum brightness is set to greater than 20 then the system dims to the set minimum brightnes...

Page 11: ...t polarity Cause 2 1 10 V control cables have short circuited Eliminate short circuit Lamps switch to maximum brightness No dimming is possible Cause 1 10 V control cables are interrupted or not connected Connect the control cables correctly 6 4 Accessories Installation box Art No FM EBG eNet server Art No ENET SERVER 6 5 Warranty We reserve the right to make technical and formal changes to the pr...