V1.00/EN/00709718 [Thyristor power switch TYA S201]
63
6 Special device functions
6.1.1 Teach-In
Depending on the configuration of the parameter "Load monit. Teach-In",
Teach-In (i.e. determination of the load measured values in the OK state) is ei-
ther performed once automatically after power ON or automatically and cycli-
cally, repeatedly every minute, or manually.
"Manual"
teach-in
For "Manual Teach-In", the power controller must be told once after the work-
ing point has been reached that it is now to perform the Teach-In.
This can be performed in the operating level or in manual mode.
v
v
Chapter 6.2.2 "Configuring Teach-In (prerequisite for Teach-In in manual
mode)"
In this variant of Teach-In, the Teach-In values are then permanently saved.
Teach-In does not need to be performed again
when the power controller is switched off and on again.
Teach-In can be repeated whenever necessary. The old Teach-In values are
then overwritten by the new ones.
The Teach-In values are only deleted if the load monitoring Teach-In parameter
is explicitly configured to "Manual Teach-In" or when the default setting is ap-
plied. Teach-In is not affected when
other parameters are reconfigured.
If "Manual Teach-In" has been configured but no Teach-In has been conduct-
ed, the message "Teach-In load monitoring!" appears on the display as a re-
minder.
"Manual Teach-In" can only be performed on the device itself, not via the set-
up program.
Teach-in
"Automatically
(once)"
"Automatically once" means that the Teach-In values are temporarily saved af-
ter each power ON. This setting is suitable only for heating elements with a
temperature coefficient TC
≈
1.
When the power controller is disconnected from the mains voltage, the Teach-
In values are deleted again. After another power ON, load monitoring therefore
remains inactive until a new Teach-In process is performed.
Teach-in
"Automatic (cy-
clically)"
"Automatically (cyclically)" means that the Teach-In values are temporarily
saved again at intervals of 1 minute. This setting is particularly suitable for SIC
heating elements as in this case the resistance in the load point changes with
time due to aging.
When the power controller is disconnected from the mains voltage, the Teach-
In values detected last are deleted and recalculated once mains voltage sup-
ply has returned.
H
The determined Teach-In values are also transferred when the setup data of
one power controller is transferred to another.
H
To ensure that the load ratios are recorded precisely for later operation, only
perform the Teach-In process at a load current of at least 20 % of the nominal
value!
Summary of Contents for TYA S201
Page 14: ...1 Introduction 14 V1 00 EN 00709718 Thyristor power switch TYA S201...
Page 21: ...V1 00 EN 00709718 Thyristor power switch TYA S201 21 2 Mounting TYA S201 250A...
Page 70: ...6 Special device functions 70 V1 00 EN 00709718 Thyristor power switch TYA S201...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00709718 Thyristor power switch TYA S201...
Page 86: ...86 V1 00 EN 00709718 Thyristor power switch TYA S201 9 What to do if...