5 Configuration
52
V1.00/EN/00709718 [Thyristor power switch TYA S201]
Soft start type
With phase-angle
control
This parameter only appears if soft start is set to "Yes".
Starting from 180°, the phase control angle
α
is steadily re-
duced until a full wave has passed through.
This ends the soft start and the device switches to burst-firing
operation.
Note: If the output level is reduced to 0 % for longer than 8
seconds, a soft start is initiated again as soon as the output
level is increased once more.
With pulse groups
This setting is available in burst-firing operation mode with a
fixed cycle time and with the fastest possible cycle time.
During the soft start time, the ON/OFF ratio is
increased from 0 to a maximum of 100 %.
Soft start duration
1 to 65535 s
Specifies the duration of the soft start.
Dual energy man-
agement
Switched off
This parameter appears only for the following setting:
Cycle time: fixed (500ms),
This setting allows 2 devices to be configured so that they do
not simultaneously draw power from the mains voltage at
small output levels.
This prevents current peaks.
v
Chapter 6.4 "Duales Energiemanagement"
Device1
Device2
Value / settings
Description
k
/ bold = default setting
u
t
Softstartzeit
u
t
Taktzeit
Summary of Contents for TYA S201
Page 14: ...1 Introduction 14 V1 00 EN 00709718 Thyristor power switch TYA S201...
Page 21: ...V1 00 EN 00709718 Thyristor power switch TYA S201 21 2 Mounting TYA S201 250A...
Page 70: ...6 Special device functions 70 V1 00 EN 00709718 Thyristor power switch TYA S201...
Page 84: ...8 Error messages and alarms 84 V1 00 EN 00709718 Thyristor power switch TYA S201...
Page 86: ...86 V1 00 EN 00709718 Thyristor power switch TYA S201 9 What to do if...