12 Error messages
44
12 Error
messages
Error display (code)
Cause
Remedy
The total number of relay switching
operations has been reached.
h
Increase the total number of relay switching
operations
v
Chapter 7.11 “C 120 Limit value for relay
h
Acknowledge with the Reset key
v
Chapter 7.12 “C 121 Count for relay switching
0002
Terminal temperature
is outside the -10 to 80°C range
h
Check the ambient temperature
h
Acknowledge with the Reset key
If that does not help, send the instrument in
0003
Reference voltage
The measured value is above 999 or below
-999 and is thus outside the 3-digit display
range.
-
A/D converter error
h
Acknowledge with the Reset key
If that does not help, send the instrument in
0004
Calibration constant
The instrument must be returned to JUMO for repair.
h
Send the instrument in
v
Chapter 2.1 “Service addresses”
0005
Configuration data
Value cannot be displayed (too large or too
small)
0006
reserved
-
0007
reserved
-