7 Configuration level
28
7.10 SCL, SCH, AL LO, AL HI, OFFS, HYST1, HYST2
7.11 C 120 Limit value for relay switching operations
Function
Comment
Value range
(factory
setting in bold)
SCL
lower limit of standard signal
only when C111 set with 52, 53, 63, 71
-1999 to 0 to 9999
SCH
upper limit of standard signal
only when C111 set with 52, 53, 63, 71
-1999 to 100 to 9999
AL LO
lower limit of the setting range for
limit value AL and warning alarm VA
Must fall within the measuring range of the
connected sensor or standard signal!
maximum adjustment: -1999 to 9999
-1999 to 9999
AL HI
upper limit of the setting range for
limit value AL and warning alarm VA
-1999 to 9999
OFFS
Measurement offset
With measurement offset, a measured value
can be corrected by a programmable value.
-1999 to 0 to 9999
HYS1
Limit value switching differential
0 to 100
0 to 1 to 100
HYS2
Warning alarm switching differential
0 to 100 (only when C119 = 1 or C119 = 2)
0 to 1 to 100
Meaning
Value range
(factory setting in bold)
Limit-value for relay switching operations
This is where the total number of permissible relay switching operations is set.
If the limit-value for relay switching operations (C121) is higher than this Limit-
value, error message 0001 is displayed immediately and the relay is de-
energized.
If "0" is set, the function is inactive.
0 to 1000 to 9999