7 Configuration level
23
7.2
C112 Setting for a double thermocouple
7.3
C113 Unit, decimal place
7.4
C114 Device function
Double thermocouple
Comment
0
no
sensor short circuit not detected!
1
yes
only available for C111 from 037 to 048
v
Chapter 7.1 “C111 Analog inputs”
Can detect a sensor short circuit
Unit, decimal place
Comment
0
°C, no decimal place
1
°C, one decimal place
2
°F, no decimal place
3
°F, one decimal place
Device function
Comment
0
Initial commissioning of TB
temperature limiter
Whatever the switching state of the relay before the power failure, the TB
remains locked when the power returns.
1
Temperature limiter TB
Release is only necessary if the temperature is exceeded
2
Temperature monitor TW
Automatic release
A
When the unit changes to °F, the measurement is
converted. All other measurement-related values,
such as AL, are unchanged!
Summary of Contents for safetyM TB/TW
Page 19: ...5 Commissioning the instrument 17 2011 12 31...
Page 42: ...9 DIN approved probes 2011 12 31 40...
Page 50: ...13 What if 2011 12 31 48...
Page 51: ......