33
9 Configuration
Input/output 1
Input/output 1 > IO-Link
Input/output 1 > analog output 1
Totalizer
cm³, l, m³, ft³, us-
gal, imp.gal
l
System unit for these parameters.
Temperature
°C, °F
C
Unit for this parameter in the process value
display
The output signal is always output in °C re-
gardless of this setting.
Parameter
Value
Default setting
Description
Parameter
Value
Default setting
Description
I/O Pin 1
IO-Link, analog
output, digital out-
put
IO-Link
Parameter function.
Parameter
Value
Default setting
Description
Application-spe-
cific marking
JUMO
flowTRANS US
W02
TAG designation (text input with max. 32
characters possible).
System designa-
tion
***
TAG designation (text input with max. 32
characters possible).
Location identifi-
cation code
***
TAG designation (text input with max. 32
characters possible).
Process data for-
mat
Floating point,
whole number
Floating point
IO-Link output format of process data.
Activate event
Inactive; Process
Data (PD) invalid;
Device (D) defec-
tive; D defective &
PD invalid; Appli-
cation-spec.
Events (AE); AE
& PD invalid; AE
& D defective; AE,
D defective & PD
invalid
Inactive
Events are passed on to the IO-Link master.
Determine measures on an application-spe-
cific basis.
Parameter
Value
Default setting
Description
Function
Inactive, current
output, voltage
output
Current output
Parameter function.
Parameter
I/O Pin 1
must be configured as
an
analog output
.
Output signal
Flow, tempera-
ture, pressure
Flow
Parameter output signal.
Scaling start
Input range:
0.000
Process value for the current output (4 mA)
or the voltage output (0 V).
-99999 to 99999
Scaling end
Input range:
Max
device mea-
suring range
Process value for the current output (20 mA)
or the voltage output (10 V).
-99999 to 99999