26 Configuration level (not instrument-specific)
76
26.4 Controller options - C211
*
The factory-set parameters are shown in the position boxes.
1
Only effective if “1” is configured in C214c and / or “1” in C214d ->
controller 2 or controller 1.
2
If the function “K1 (output 1) Modulating controller” is selected, then the
function “K2 (output 2) Modulating controller” must also be selected
(and the other way round).
3
Function description,
Chapter 28 “Manual operation”, page 86.
4
Not possible if limit comparators have been configured.
5
The entry depends on the measurement variable that was configured
(depends on rAnG).
a
b
c
d
C211*
2
2
x
0
Function K1
1
(output 1)
I
I
I
I
off
0
I
I
I
Limit controller
1
I
I
I
Pulse width controller
2
I
I
I
Pulse frequency controller
3
I
I
I
Modulating controller
2
4
I
I
I
Proportional controller
5
I
I
I
I
I
I
Function K2
1
(output 2)
I
I
I
off
0
I
I
Limit controller
1
I
I
Pulse width controller
2
I
I
Pulse frequency controller
3
I
I
Modulating controller
2
4
I
I
Proportional controller
5
I
I
I
I
Calibration procedure
5
I
I
Zero point for 1-point calibration, process value output not frozen
0
I
Zero point for 1-point calibration, process value output frozen
1
I
End value for 1-point calibration, process value output not frozen
2
I
End value for 1-point calibration, process value output frozen
3
I
2-point calibration, process value output not frozen
4
I
2-point calibration, process value output frozen
5
I
I
Manual operation
3
I
Manual operation off
0
Manual operation enabled, switched
4
1
Manual operation enabled, only while the key is pressed
2
Simulated process value output 1
3
Simulated process value output 2
4