Universal Single- and Double-channels Transmitters to DIN Rail with HART Communication

3.3 Dimensional drawings

Case with mounted spring terminals:

Case with mounted screw terminals:

112,5

22,5

118,5

112,5

22,5

107,5

4. Installation, operation and maintenance
4.1 Installation and commissioning

4.1.1 General

After  mounting  and  correct  connection,  switch  on  the  power 
supply.
During  the  installation  of  transmitters  in  environment  with 
higher  level  of  interference,  protection  of  transmitters 
against  interference  and  induced  overvoltage  must  be 
ensured.  According  to  the  standard  engineering  practice, 
it  is  recommended  to  separate  signal  and  power  wires  into 
separate gutters and use shielded signal cables with twisted 
wires.  In  case  of  outdoor  wires,  it  is  necessary  to  solve  the 
overvoltage  protection  of  the  transmitter  as  a  part  of  overall 
solution of protecting system from the effects of atmospheric 
electricity.

4.1.2 Special conditions for use of intrinsically safe 
version (code EI1)  
        II (1) G [Ex ia Ga] IIC 
        II (1) D [Ex ia Da] IIIC

The  transmitter  P5335  for  installation  for  DIN  rail  may 
not  be  installed  in  any  explosion  hazard  environment. 
This  restriction  also  applies  to  version  P5335  Lxx  EI1. 

Only input and output wires of the version P5335 Lxx EI1 may 
lead  to  explosion  hazard  environment.  The  transmitter  input 
and  output  may  be  connected  only  to  suitable  associated 
apparatus or to simple apparatus complying with the standard 
EN 60079-14 when respecting the restricting conditions. When 
installing  a  transmitter,  it  is  necessary  to  separate  terminals 
of  intrinsically  safe  circuits  by  air  gaps  at  least  50  mm  from 
terminals of the circuits that are not intrinsically safe (see EN 
60079-11). In case of a double-channel version P5335 L2x EI1 
both channels shall be included in intrinsically safe circuits.

4.1.3 Electrical connection

Power

supply

HART Modem /

/ Configurator

R

L

250 Ohm

mA

x3

x6

x4 x5

x1

x2

x3

x6

x4 x5

3W

4W

4W

CJC

CJC

x4 x5

x3

x6

x4 x5

x3

x6

x4 x5

x3

x6

x4 x5

x3

x6

x4 x5

1

2

1

2

1

2

x3

x6

x4 x5

x3

x6

x4 x5

3W

4W

4W

U

x3

x6

x4 x5

U

2

U

1

RTD

Output:

Input:

Resistance

TC, CJC

compensation

terminal

(Note 2)

TC, external CJC

TC, const.CJC

(Note 3)

Voltage, difference

or average

TC, difference

or average ,

const.CJC

(Note 4)

TC, difference

or average ,

external CJC

RTD, difference

or average

Voltage

Output, 1.channel

(terminals 11,12)

Output, 2.channel

(terminals 21,22)

Input, 1.channel

(terminals 13,14,15,16)

Input, 2.channel

(terminals 23,24,25,26)

Note 1

Summary of Contents for P5335

Page 1: ...820 www jsp cz SK 841 04 Bratislava 421 2 6030 1089 www jsp sk Universal input for all common resistance and thermocouple temperature sensors linear resistance and mV Accuracy 0 05 Measurement of dif...

Page 2: ...allation operation and maintenance 5 4 1 Installation and commissioning 5 4 2 Measurement of thermocouple temperature sensors using transmitter P5335 Lxx for a DIN rail 6 4 3 Description of setting an...

Page 3: ...balen v ochrann m krytu a za p edpokladu identifika n m t tkem se zna kou v stupn kontroly V robek nesm b t vystaven p m mu d vibrac a r z p i p eprav 1 5 Storage The products shall be stored at tempe...

Page 4: ...sensors In other cases the resistance of input wires is compensated automatically In case of three and four wire connection there can be entered the maximal values of resistance of the line and the m...

Page 5: ...II 1 D Ex ia Da IIIC The transmitter P5335 for installation for DIN rail may not be installed in any explosion hazard environment This restriction also applies to version P5335 Lxx EI1 Only input and...

Page 6: ...o the transmitter terminals or in a remote terminal box that is connected with the transmitter using a copper line In both cases it is necessary to install the compensation sensor so that it measures...

Page 7: ...setting and control can be found in the instructions manual to the configurator The transmitter in design EI1 can be configured using the communicator HARTConf only if the transmitter communicator an...

Page 8: ...m C Voltage 10 V 0 5 V C Characteristics Linear with temperature or linear with input quantity other upon request Adjustability of the range 16 bit P estavitelnost rozp t 1 to 100 of the basic range...

Page 9: ...ompensation terminal CTB1 L11 Single channel transmitter with removable screw terminals L12 Single channel transmitter with removable spring terminals L20 Double channel transmitter with removable scr...

Page 10: ...10 Universal Single and Double channels Transmitters to DIN Rail with HART Communication 8 Appendix 8 1 Declaration of conformity explosion hazard environment version code EI1...

Page 11: ...JSP Industrial Controls JSP s r o Raisova 547 506 01 Ji n Czech Republic 420 493 760 811 export jsp cz www jsp cz Your Supplier Contacts...

Reviews: