Figure 4. Hearth, Trim and Wall clearances.
Clearance to Combustible
Materials
A combustible material is anything that can
burn (i.e. sheet rock, wallpaper, wood, fabrics etc.).
These surfaces are not limited to those that are
visible and also include materials that may be
behind non-combustibles.
If you are unsure of the combustible nature of a
material, consult your local fire officials. “Fire
Resistant” materials are considered combustible:
they are difficult to ignite, but will burn. “Fire-rated”
sheet rock is also considered combustible.
The following clearances and hearth specifications
are the minimum requirements for installation into
a masonry or factory built fireplace. Mantel and
wall clearances will vary, depending upon the
fireplace facing and riser height, if needed. Use the
tables and illustrations in figs. 4 and 5 to determine
the minimum clearances for your installation.
Hearth Requirements
Hearth protection in front of the GI 350 DV must be
composed of any noncombustible material. It must
extend 16” forward of the firebox glass panel and
extend 18” to either side of the fireplace centerline.
See fig. 4.
Fireplace Facing Options
Jøtul Cast Iron Surround -
34 1/2” x 24 1/2”
w/ Plinth - 34 1/2” x 26 1/2”
w/Wide Surround Panel
-
38” x 26”
w Plinth Extensions - 38 1/2” x 28”
Steel Door Kits - includes Surround Panels
38” Wide x 28” High
SCAN 65i Surround Assembly
- with 1” Riser: 40” Wide x 27” High
- with 2” Riser: 40” Wide x 28” High
E
C
B
D
A
A:
A:
A:
A:
A: Hearth Protection Width - 18” from centerline.
B:
B:
B:
B:
B: Hearth Protection Depth - 16”
C:
C:
C:
C:
C: Side Trim Clearance, 1.5” thick (25 mm) Shown mea-
sured from fireplace centerline = 1” from Surround.
D:
D:
D:
D:
D: Side Room Wall Clearance shown measured from
the fireplace centerline = 24” from Surround.
E:
E:
E:
E:
E: Top Trim Clearance = Same as 3.5” deep mantel-
See fig. 5.
Table 1. Hearth, Trim and Wall clearances.
A
B
C
D
E
18”
16”
18 1/4”
41 1/4”
35”
18”
16”
41 1/4”
37”
18”
16”
20”
43”
38”
18”
16”
21”
44”
18”
16”
44”
Surround
Type
Jøtul
Cast Iron
Jøtul
Cast Iron
w/ Plinth
Steel
Double
Doors
Scan 65i
w/ Mantel
Heat Shield
Scan 65i
without
Mantel
Heat Shield
37”: 1”
Riser
38”: 2”
Riser
Use
noncom-
bustible
materials
only.
Use
noncom-
bustible
materials
only.
20”
w/ Wide
Surround
18 1/4”