Chimney Connection
This insert must be connected to a code-approved
masonry chimney or listed factory-built fireplace
chimney with a direct (positive) flue connector into the
first chimney liner section. The chimney size should not
be less than, nor more than, three times greater than
the cross-sectional area of the flue collar.
The optional Jøtul Draw-Down Adaptor Kit 156073 is
available to ease connection of the chimney liner with
the flue collar.
A positive connection must be made between the
fireplace insert and the chimney by one of the following
approved methods.
U.S. Requirement:
The insert is connected to a listed stainless steel flexible
connector that extends into the first chimney flue tile
liner. A sealed block-off plate must be installed at the
damper area of the existing fireplace. See fig. 7.
For internal chimneys, (no sides of the chimney
exposed to the outside below the roofline,) a positive
connection to the first flue tile is acceptable provided
the tile is no larger than 8” x 12”.
For external chimneys (one or more sides are exposed
to the outside below the roof line, including garages),
a positive connection to the first flue tile is acceptable
provided the tile is no larger than
8” x 8”.
A 6”, 7”, or 8” stainless steel liner, extending the full
height of the chimney, is required for all installations
where the flue tile is greater than 8” x 12” for internal
chimneys, or 9” x 8” for external chimneys.
Canada Requirement:
The insert must be installed with a continuous
chimney liner of 6” (152 mm) diameter extending
from the fireplace insert to the top of the chimney.
The chimney liner must conform to the Class 3
requirements of CAN/ULC-S635, Standard for Lining
Systems for Existing Masonry or Factory-Built
Chimneys and Vents, or CAN/ULC-S640, Standard for
Lining Systems for New Masonry Chimneys.
See fig. 8.
Do not use aluminum or galvanized steel pipe for
chimney connection components - these materials
are not suitable for use with solid fuel.
Flex
Connector
Pipe
extends at
least into
the first
flue tile
Figure 7. Positive Chimney Connection - U.S.
Attach Fireplace
Conversion
Notice Plate
to Rear Wall of
Fireplace