16
Jøtul C
350
Winterport 138376_Rev_Q 2/17
Blower Operation
Access the blower control panel by lifting the cast
iron lower grille up off the insert.
The dual blowers will enhance heat circulation
around the firebox and out into the room. In the
Automatic setting, the blowers are controlled by
a heat activated switch (snapstat) that will only
function when the speed control is ON. After the fire
has been burning for a time, the snapstat will react
to the heat and activate the blowers. Conversely, the
blower will continue to operate until the snapstat
cools as the fire wanes. The blowers will then shut
off automatically.
The Manual setting overides the snapstat
functionality allowing blower operation regardless
of temperatures.
For best performance, do not turn the switch on
until after the fire is well-established.
If the blower is not needed, place the blower
control switch in the OFF position.
See Blower Maintenance section on page 19 for
further information.
THIS BLOWER MUST BE
ELECTRICALLY GROUNDED IN
ACCORDANCE WITH LOCAL CODES
OR, IN THE ABSENCE OF LOCAL
CODES, WITH THE CURRENT ANSI/
NFPA 70, NATIONAL ELECTRICAL
CODE OR CSA C22.1-CANADIAN
ELECTRICAL CODE.
THIS UNIT IS SUPPLIED WITH
A THREE-PRONG (GROUNDING)
PLUG FOR PROTECTION AGAINST
SHOCK HAZARD AND SHOULD
BE PLUGGED DIRECTLY INTO A
PROPERLY GROUNDED THREE-
PRONG RECEPTACLE. DO NOT
CUT OR REMOVE THE GROUNDING
PRONG FROM THE PLUG.
ALWAYS DISCONNECT THE POWER
SUPPLY WHEN PERFORMING ANY
SERVICE ON THE FIREPLACE
INSERT.
Figure 19. C 350 Wiring diagram.
Figure 18. Blower and speed controls.
Color Key
BR - Brown
BL - Blue
BK - Black
GY - Gray
G - Green
Creosote cont’d.
A chimney flue located within the home interior
will benefit from the insulating characteristics of the
building itself. Consequently, the flue system will be
less conducive to condensation of unburned gases and
minimal creosote accumulation will result..
As a general rule, try to avoid burning the insert at
the lowest air control settings. Although a low setting
will prolong burn time, it may also result in incomplete
combustion. In reducing the fire intensity, draft is
weakened and the chimney flue cools. This, together
with the increase in unburned gases, leads to rapid
creosote accumulation.