15
User and Installation Manual
Compact MPA
4.4 EXTERNAL INTERFACES
The Compact MPA PA/GA system is equipped with various control outputs for external equipment. This is intended for
additional warnings and indicators. Ref. drawing in 9.3.
Terminals
Name
Description
Input/output
Interface
Voltage
Current /
Impedance
1 – 2
A ~
Loudspeaker loop,
Zone 1
Output
100VAC
2.5A
3 – 4
B ~
100VAC
2.5A
5 – 6
A ~
100VAC
2.5A
7 – 8
B ~
100VAC
2.5A
9-10
A ~
Loudspeaker loop,
Zone 2
Output
100VAC
2.5A
11-12
B ~
100VAC
2.5A
13-14
A ~
100VAC
2.5A
15-16
B ~
100VAC
2.5A
17-18
A ~
Loudspeaker loop,
Zone 3
Output
100VAC
2.5A
19-20
B ~
100VAC
2.5A
21-22
A ~
100VAC
2.5A
23-24
B ~
100VAC
2.5A
25-26
A ~
Loudspeaker loop,
Zone 4
Output
100VAC
2.5A
27-28
B ~
100VAC
2.5A
29-30
A ~
100VAC
2.5A
31-32
B ~
100VAC
2.5A
33-34
A ~
Loudspeaker loop,
Zone 5
Output
100VAC
2.5A
35-36
B ~
100VAC
2.5A
37-38
A ~
100VAC
2.5A
39-40
B ~
100VAC
2.5A
41-42
A ~
Loudspeaker loop,
Zone 6
Output
100VAC
2.5A
43-44
B ~
100VAC
2.5A
45-46
A ~
100VAC
2.5A
47-48
B ~
100VAC
2.5A
49
Z1ref+24V
Volume Override control
outputs
Output
Open collector source/
sink
24VDC
40 mA
51
Z1
53
Z3ref+24V
Open collector source/
sink
24VDC
40 mA
55
Z3
57
Z5ref+24V
Open collector source/
sink
24VDC
40 mA
59
Z5
61
Not in Use
63
Not in Use
50
Z2ref+24V
Volume Override control
outputs
Output
Open collector source/
sink
24VDC
40 mA
52
Z2
54
Z4ref+24V
Open collector source/
sink
24VDC
40 mA
56
Z4
58
Z6ref+24V
Open collector source/
sink
24VDC
40 mA
60
Z6
62
Not in Use
64
Not in Use
65
Al. 1 ref -
Direct Alarm inputs
Input
Dry contact input
≈20VDC
2 mA
67
Al. 1
69
Al. 2 ref -
≈20VDC
2 mA
71
Al. 2
73
Al. 3 ref -
≈20VDC
2 mA
75
Al. 3
77
Al. 4 ref -
≈20VDC
2 mA
79
Al. 4
66
Al. 1 ref +
Alarm status outputs
Output
Open collector source/
sink
24VDC
40 mA
68
Al. 1
70
Al. 2 ref +
24VDC
40 mA
72
Al. 2
74
Al. 3 ref +
24VDC
40 mA
76
Al. 3
78
Al. 4 ref +
24VDC
40 mA
80
Al. 4
81
Alarm Sync IN
Alarm sequence input
Input
Dry contact input
≈20VDC
2 mA
83
Alarm Sync Ref-
85
EMPA_NO
Emergency PA active
output, Normally Open
Output
Dry contact output
--
0.3 A
87
EMPA_CO
Summary of Contents for MPA 1600
Page 21: ...22 User and Installation Manual Compact MPA DNH HP15T...
Page 51: ...52 User and Installation Manual Compact MPA 9 2 WALL BRACKET KIT...
Page 53: ...54 User and Installation Manual Compact MPA 9 3 COMPACT MPA CABINET EXTERNAL CONNECTION...
Page 54: ...55 User and Installation Manual Compact MPA...
Page 62: ...www jotron com...