device leaves the factory fully wired. It only needs to be plugged into the electric
mains, 230V/ ~1 / 50Hz + PE. Power must be brought to the socket installed on the module by
an IEC 60320 C13 type plug. A residual current device must be installed upstream according to
standards in force. The socket on the panel is equipped with a fuse.
6.6 ELECTRIC POWER SUPPLY
The ON/OFF switch indicates when the device is powered.
ATTENTION!
Using the supplied rope for the link to the net or provide one of equal section
always composed by F,N and T. Before making any connections, make sure the
mains voltage complies with what is shown on the label.
It has also to be provided:
• A four polar linking rope on alarm contact not in tension for the takeover of the state signal of
the device.
• A six polar linking rope on signal contact of alarm reset and of the comunication serial line.
The plugs of these contacts are provided with the form.
Example installation.