20
07.3 ASSEMBLY SEQUENCE
Install the fireplace as follows:
UNIVERSALJOLLY EVO 4S models
1A.
Organize the air intakes as indicated at point 6.
2A.
Create the fan compartment according to the dimensions
given in the drawings (LxHxP= 35x20x40 cm,
F
ig
.1-2
).
3A.
Make a hole for power cable entry.
4A.
Prepare a convector air inlet to discharge the heat (minimum
surface 450 cm
2
) in the upper section of the cladding, about
1.5 m above the fireplace (see
CHAP.07.5 - EXAMPLE
OF FIREPLACE INSTALLED AND CLADDED
).
Before fitting the fireplace, fix the support (see FIG 1 and
CHAP.06.3 - COMPONENTS
) on the cladding surface
to create a sturdy base and seal using heat-resistant
silicone along the contact perimeter between the support
base and the fireplace to prevent the fan from suctioning
air from the flue.
To prevent heat loss, it is recommended to insulate the
fireplace before fitting in place using the insulating material
supplied.
5.
If the air is to be ducted into other rooms using the relative optional accessories, before connecting it to the flue, prepare the holes
for the ducting tubes on the extractor hood, the back of the device, or wherever it is most convenient based on the installation
requirements; bear in mind that the passage of air intake ducts inside the fume evacuation system is prohibited (
F
ig
.4
).
6.
Organize the air intakes by choosing one of these options:
a) Combustion air intake connected with the outside, with hot air recycle into the room.
Prepare an inlet for the combustion air communicating with outdoors via a 100 mm Ø aluminum pipe with a maximum length of 100 cm to
connect via the provided connector (see
CHAP.06.3
)
under the fireplace base. To fix the connector to the fireplace brake and
remove the pre-cut part (see
CHAP.07.5 - EXAMPLE OF FIREPLACE INSTALLED AND CLADDED
).
SUPERJOLLY EVO 4S models
1B.
When the fireplace arrives, lie it on the floor or lift with a crane,
then apply the legs using the supplied screws to fasten in
place (
F
ig
. 3)
.
2B.
During this phase, it is advisable to assemble the fan
positioning it in its designated seat and fastening it as
indicated in points 12 to 14.
3B.
Position the device where it is to be installed, bearing in mind
that the installation of the device must guarantee easy access
for cleaning its parts, the circulation fan, the exhaust fumes
ducting and the flue.
1A.
Organize the air intakes as indicated at point 6.
F
ig
. 2
6
F
ig
. 3
350
Presa aria esterna
(200x200 mm)
40
0
20
F
ig
. 1
F
ig
. 4
Fan compartment
dim. 350x400x200 mm
Existing fireplace
walls
Existing fireplace
walls
Existing fireplace
walls
Optional guide
support
Smoothing with
cement
Rock wool
Depth 200 mm
Power cable entry