Jolly Mec SUPERJOLLY EVO 68X50 4S Installation, Use And Maintenance Manual Download Page 19

ENGLISH

 

07.2 

INSTALLATION ROOM VENTILATION

According to reference regulation UNI10683, 4 Pa depression must be verified between the installation room interior and exterior. 

Prepare adequate ventilation openings in the room where the product is installed to permit at least 50 m

3

/h clean comburent air flow not 

taken from polluted rooms. The ventilation openings, if fitted with insect-proof mesh, must be easily removable and undergo periodic 

cleaning to ensure clear air flow passage. 

As per the fuel product exhaust system, air vents are also extremely important and must be given the appropriate 

consideration and respect. 

The installer is directly liable for all electrical system parts, generation hook-up to the system, ventilation and the fume 

exhaust system and MUST, at the end of installation work, issue a declaration of conformity as per Ministerial Decree 37/08. 
On the other hand, the purchaser MUST assign all work to a qualified professional technician.
The device must be installed and used in accordance with all local and national laws and EC Regulations.

WARNING

The use of counter slope elements is forbidden.The flue union must have a constant section and allow soot to be collected and swept 

away. Changes in cross-section are only allowed at the outlet of the heat generator: the use of adaptors on the coupling with the chimney 

flue is prohibited.
Running other air ducts and installation pipes inside the exhaust pipes, even if oversized, is forbidden.
One or more airtight reading points are recommended on the flue to check emissions after installation and measure draught.
Supporting the weight of the flue with the appliance union is strictly forbidden. Use specific stands or independent supports for this 

purpose.
To install other combustion devices in the same room where the appliance is installed, refer to UNI 10683 and UNI 7129 installation 

regulations.
The minimum fireplace height must be over 3,0 m.
Installation of external fireplaces must be performed using insulated double-walled pipes, to prevent the formation of condensate; it must 

also be possible to inspect the base of the fireplace for routine maintenance which must be done at least once a year.
A minimum flue draught between 10 and 14 Pa must be guaranteed. This value must be measured using specific and controlled 

instruments each time the appliance and flue undergo maintenance.

The appliance could malfunction in very strong windy conditions, with the chimney cap installed in the reflux area (see 

F

ig

. 2

, zone 

bordered by the dotted line A for roofs with ß>10° slant) of the roof, or without complying with the distances foreseen by UNI 10683.

The external air intakes must be made so that they cannot get accidentally covered and if they have an insect 

protection mesh they must be cleaned periodically to prevent clogging with dust and dirt, especially in periods with intense 

pollen concentrations.

NOTE

.

130 cm

.

50 cm

ß>10°

A

90°

F

ig

. 2

19

Summary of Contents for SUPERJOLLY EVO 68X50 4S

Page 1: ...ept by the purchaser Wood burning air inset fireplace UNIVERSALJOLLYEVO604S UNIVERSALJOLLYEVO68X504S UNIVERSALJOLLYEVO68X584S UNIVERSALJOLLYEVO804S SUPERJOLLYEVO604S SUPERJOLLYEVO68X504S SUPERJOLLYJOL...

Page 2: ...y read and keep this sheet before using the equipment This sheet provides necessary information and suggestions on how to correctly install use clean and maintain the product Knowing and observing the...

Page 3: ...NSPORT 10 CHAP 04 ECOLOGICAL REGULATIONS 11 04 1 DISPOSAL OF THE MACHINE 11 CHAP 05 DESCRIPTION 12 05 1 PRODUCT PRESENTATION 12 05 2 PRODUCT IDENTIFICATION 13 CHAP 06 TECHNICAL DATA 14 06 1 HOMOLOGATI...

Page 4: ...itten permission of Jolly Mec Caminetti S p A The technical directions for installation contained in this manual should be considered as basic requirements Regulations in some countries may be more re...

Page 5: ...EN 60335 1 Household and similar electrical appliances Safety General requirements EN 60335 2 102 Household and similar electrical appliances Safety Particular requirements for gas oil and solid fuel...

Page 6: ...ight to make modifications to the product and consequently the relative manual without any obligation to update previous editions 01 5 MANUFACTURER S LIABILITY AND WARRANTY CONDITIONS Upon the deliver...

Page 7: ...ry or mental capabilities or lacking the experience or the needed knowledge can use the device only under surveillance or having been instructed on the device safe use and on the understanding of the...

Page 8: ...ation defects arise during the optional Commisisoning service the specialised Technical Service Center can refuse to endorse use of the product for safety reasons and submit a written Servicing Report...

Page 9: ...produce its systems with the greatest competence regarding safety and consulting all the directives laws and regulations available there are still if minor some residual risks during the phases of TRA...

Page 10: ...retailer as soon as possible 03 2 LIFTING AND TRANSPORT Personnel in charge of handling the product must have read and thoroughly understood the safety prescriptions in CHAP 02 ACCIDENT PREVENTION SA...

Page 11: ...tive 2012 19 UE waste electrical and electronic equipment WEEE information for users The crossed out wastebasket symbol on the appliance means that at the end of its useful lifespan the product must b...

Page 12: ...S inset fireplace also feature a combustion chamber in Fireflector HD which in addition to improving the aesthetic appearance also contribute to guaranteeing a high chamber temperatures level hence re...

Page 13: ...os CO emissioni CO emissions CO emission Emission de CO Emisi n de CO Tensione Frequenza nominale Rated voltage frequency Spannung Nennfrequenz Tension Fr quence nominale Tensi n Frecuencia nominal Te...

Page 14: ...400 1500 mm Energy efficiency class A A A A Description Superjolly EVO 60 4S Superjolly EVO 68X50 4S Superjolly EVO 68X58 4S Superjolly EVO 80 4S UM Burnt heat output 7 4 8 6 9 9 11 5 kW Nominal heat...

Page 15: ...e best fuel is air dried untreated wood with a humidity of 15 18 beech hornbeam oak and acacia are highly recommended The wood must be stored outdoors in a protected dry and well ventilated area Exces...

Page 16: ...1B SuperJolly EVO 4S models 2 Electronic control unit 3 Rock wool matting for boiler insulation For UniversalJolly EVO 4S only 4 Heat proof glove 5 Fan 410 m3 h 6 Support various models only for Univ...

Page 17: ...UNIVERSALJOLLY EVO 68X58 4S 680 442 5 585 5 472 5 UNIVERSALJOLLY EVO 80 4S 800 562 5 585 5 472 5 SUPERJOLLY EVO 60 4S 600 362 5 500 5 472 5 SUPERJOLLY EVO 68X50 4S 680 442 5 500 5 472 5 SUPERJOLLY EVO...

Page 18: ...nternal section which is preferably circular square or rectangular sections must have rounded corners with a radius of no less than 20 mm must have an internal section that is constant free and indepe...

Page 19: ...d Running other air ducts and installation pipes inside the exhaust pipes even if oversized is forbidden One or more airtight reading points are recommended on the flue to check emissions after instal...

Page 20: ...the passage of air intake ducts inside the fume evacuation system is prohibited Fig 4 6 Organize the air intakes by choosing one of these options a Combustion air intake connected with the outside wit...

Page 21: ...he outside in the room of the installation Then you have to take apart the central opening b Fig 5 it is necessary to screw off the screw and to remove the combustion air regulation lever When the cen...

Page 22: ...ENANCE Repeat these operations in the reverse order to reposition it 8 If possible pad with rock wool between the existing chimney flue and the stainless steel pipe to prevent a return of the flue gas...

Page 23: ...ctrically connected the probe has been connected to the control unit and the device operating functions have been tested close all access to the compartment using the parts indicated in section 12 fol...

Page 24: ...amic fibre rock wool and can come in different forms sheets mattresses Its specific weight must be equal or greater than 245 kg m3 with a temperature threshold of about 1000 C and thermal conductivity...

Page 25: ...vailable 1 Flammable Wall 2 Flammable floor 3 Flammable ceiling 4 Fireplace cladding in not flammable material Installation distances from flammable materials A Minimum air distance from inflammable s...

Page 26: ...le exhaust vents for hot air at least 2 x 80 cm Regulation of comburent air Flexible aluminium pipes for hot air ducting 100 mm Recirculation grid obligatory hood 450 cm 100 mm from the ceiling Fume e...

Page 27: ...pipes to deliver the air is very dangerous because the high temperatures could deform them and generate harmful gases Where the ducting pipes cannot be embedded they can be concealed with a false cei...

Page 28: ...onnection or Y connection optional and connect the two top outlets as well as the ducting WARNING Fig 2 Installation with internal fan air intake Provide for recirculation of hot air in the room see C...

Page 29: ...n and functioning then turn the comburent air regulating lever to position 1 Fig 1 Small pieces of wood maximum LxHxW 35x4x4 cm must be used to light the fire stacking them on the fireplace grate as s...

Page 30: ...arge To achieve the declared nominal heat output adjust the unit as follows Model Wood quantity Dimension Comburent air record Rechar ging time Universaljolly EVO 60 4S Superjolly EVO 60 4S 2 identica...

Page 31: ...the same room excluded of the type C according to UNI 10683 The device must not be used to burn anything other than the recommended fuels as the combustion by products could corrode the device or the...

Page 32: ...grate and use a brush or sharp tool to clean away any residues A vacuum cleaner can also be used Put everything back in place Glass Use specific products Be careful not to use overly aggressive produc...

Page 33: ...carry out these operations the appliance must be disconnected from the mains wait until the appliance is cold and comply rigorously with the safety regulations in force WARNING Flue gas deflector To r...

Page 34: ...excluded of the type C according to UNI 10683 Load the wood when there is no flame Place the baffle correctly see CHAP 08 5 ASSEMBLY SEQUENCE The outside air inlets and or the flue are partially or co...

Page 35: ...ENGLISH NOTES 35...

Page 36: ...SM140 EN REV01 2019_01 Via S Giuseppe 2 24060 Telgate Bg Italy Tel 39 035 83 59 211 Fax 39 035 83 59 203 www jolly mec it info jolly mec it...

Reviews: