9
Fastening the indoor unit to the ceiling
When fastening, make sure it is completely horizontal, or
very slightly tilted towards the drain, so as to avoid possible
condensed water leaks (use a bubble level).
It is extremely important to be very careful with the support
of the indoor unit on the ceiling.
Make sure the ceiling is strong enough to support the weight
of the unit.
Before hanging, check the strength of each suspension bolt
installed.
Outdoor unit air ducts
1.- Connect the ducts, isolating them from the unit by means
of a flexible hose, preferably of non-flammable material, so
as to avoid the transmission of vibrations of the unit. If the
ducts are made of flexible material, they do not transmit
vibrations.
2.- On units VCH 45A, 60A, 75A and 90A, two different ducts
must be installed, one for each fan up to the discharge,
to avoid the recirculation of air.
3.- If the outdoor air coil air discharge is carried out through
the ducts, it is convenient to have the first 1-meter section
made of galvanized sheeting so as to avoid deterioration
due to a possible creeping of drops.
Indoor unit air ducts
1.- Connect the ducts, isolating them from the unit by means
of a flexible hose, preferably of non-flammable material,
so as to avoid the transmission of vibrations of the
unit.
If the ducts are made of flexible material, they do not
transmit vibrations.
2.- It is recommendable to install a damper at each by-pass
of the discharge duct for the purpose of carrying out a
correct balance of the system.
3.- Leave easy access for cleaning and changing the air
filters.
Drain connections, VCH 20 to 90A outdoor
unit
Install the drain pipes of each tray through a siphon.
The drain line must have a minimum slope of 2 cm. per each
metre in length.
The unit connections are made of copper piping with an
exterior diameter of 28.5.
Attention:
When the heat pump is operating at outdoor temperatures
of less than 5° C, the drain pipe could be obstructed due to
freezing.
So, if installed in exteriors, it is convenient to take this pos-
sibility into account, installing an electric heater at the drain
connection and around the antivibratory elements of the
compressor, connecting same electrically as per the dia-
grams herein.
Drain connections, VIR 25 to 90A indoor unit
It is necessary to connect a condensed water drain pipe to
the evaporating unit.
Install the drain pipe through a siphon.
Leave a minimum level difference of 25 mm. between
the height of the unit connection and the line after the si-
phon.
An access must be left so as to fill the siphon with water at
the beginning of each season.
The drain line must have a minimum slope of 2 cm. per each
metre in length.
Insulate the condensed water drain pipe so as to avoid leaks
and damaging the floor.
Drain pipe insulation
Insulate the condensed water drain pipe so as to avoid leaks
and damaging the floor.
Make sure water evacuation is being carried out correctly.
Interconnecting units
The installation of a unit comprises:
- Assembly of the unit.
- Connection of refrigerant pipes.
- Wiring of the unit.
When installing Split units, make sure the cooling circuit is
completely sealed after assembly, for the purpose of avoid-
ing leaks.
This will contribute to achieving maximum performance with
minimum consumption, and will avoid serious damage to the
unit. Furthermore, this is an ecological precaution.
Installation of interconnecting pipes
The length of the interconnecting pipes of the units should
be as short as possible.
The maximum admissible distances to the circuit and the
standard pipe diameter are indicated in the tables and
graphs below (without changing the pipe outlet diameter of
the units).
When there are horizontal sections of over 20 metres, it is
convenient to have the suction line tilt 2% in the direction of
the compressor.
- The maximum allowable flow in any section is 15 m/s.
- With the limitations indicated and without changing the
diameter of the outgoing unit pipes, no siphons are need-
ed.
- The liquid should have a minimum of 1° C of subcooling at
the intake of the expansion valve, so as to avoid accumula-
tion of gas in the ascending liquid lines before entering the
expansion system.
Summary of Contents for York VCH 20A
Page 17: ...17 Technical characteristics General dimensions mm VCH 20A and 25A ...
Page 18: ...18 General dimensions mm VCH 30A and 40A ...
Page 19: ...19 General dimensions mm VCH 45A and 60A ...
Page 20: ...20 General dimensions mm VCH 75A and 90A ...
Page 21: ...21 General dimensions mm VIR 25A VIR 40A ...
Page 22: ...22 General dimensions mm VIR 45A and 60A VIR 75A and 90A ...
Page 23: ...23 Cooling diagram Variant chart ...
Page 31: ...31 Electric diagram VCH 20 25 30 40A 400 3 50 ...
Page 32: ...32 Electric diagram VCH 45 60 75 90A 400 3 50 ...
Page 33: ...33 Electric diagram VCH 45 60 75 90A 400 3 50 ...
Page 34: ...34 Configuration of switches ...
Page 43: ...43 Wiring diagram VIR 45 90 ...
Page 48: ...48 Wiring diagram Heater 10 15kW 400 3 50 VIR 25A 40A 45A and 60A ...
Page 49: ...49 Wiring diagram Heater 20 30 40kW 400 3 50 VIR 40A 45A 60A 75A and 90A ...
Page 59: ...59 VCH 20A to 40A VCH 45 to 90A ...
Page 61: ...61 Wiring diagrams ...
Page 62: ...62 Wiring diagrams ...
Page 69: ...69 Wiring diagram ...
Page 71: ......
Page 72: ...www johnsoncontrols com ...