Access Control Module
5–8
iSTAR Ultra Installation and Configuration Guide
Figure 5-5:
Reader Power - Observing Polarity
LOCK 1 Power - J2
This is one of the power inputs to the relay outputs that are jumpered as Wet LOCK 1.
It can be either 12 Vdc or 24 Vdc. It will also supplement the J4 Reader Power.
LOCK 2 Power - J3
This is one of the power inputs to the relay outputs that are jumpered as Wet LOCK 2.
It can be either 12 Vdc or 24 Vdc. It will also supplement the J4 Reader Power.
FAI and Key - J84
The FAI signal is NC and the Key signal is NO. Wire the supervised resistors as shown in
.
Figure 5-6:
FAI Signal NC and Key Signal NO