437642-UIM-C-0210

Johnson Controls Unitary Products

23

NOTES:

1. Airflow expressed in standard cubic feet per minute (CFM).

2. Return air is through side opposite motor (left side).

3. Motor voltage at 115 V.

4. Airflow through across motor side (right side) may be slightly less than the data shown above.

Table 14: 

Blower Performance CFM - Any Position (without filter) - Left Side Return

Models

Speed

Left Side Airflow Data (SCFM)

Ext. Static Pressure (in. H2O)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

040A08

High 

994 971 942 899 829 725 419 120  NA  NA 

Medium 

High  824 804 777 739 675 489 350 361  NA  NA 

Medium 

Low  757 733 694 659 575 444 399  NA  NA  NA 

Low 

707 684 641 604 495 397 282  NA  NA  NA 

060A10

High 

1371 1323 1251 1169 1086  971  843  521  NA  NA 

Medium 

High  1249 1207 1158 1098 1018  921  669  503  NA  NA 

Medium 

Low 1059 

1026 997 949 889 793 582 420  NA  NA 

Low 

854 836 809 775 717 576 464 216  NA  NA 

060A12

High 

1406 1401 1394 1379 1338 1304 1261 1202 1135 1040 

Medium 

High  1129 1126 1107 1094 1076 1047 1010  966  921  843 

Medium 

Low  970 947 933 916 890 863 827 789 741 668 

Low 

834 809 797 768 740 710 677 634 586 534 

080B12

High 

1274 1285 1255 1239 1207 1158  1111  1049  979  830 

Medium 

High  975 974 968 960 948 923 879 823 756 672 

Medium 

Low  777 771 772 762 752 734 695 651 604 529 

Low 

647 634 623 610 602 588 552 506 457 381 

080C16

High 

1825 1781 1746 1695 1641 1587 1521 1429 1330 1184 

Medium 

High  1516 1493 1482 1464 1442 1411 1343 1275 1192 1035 

Medium 

1294 1297 1271 1238 1187 1120 1083 1028  979  851 

Low 

1126 1115 

1095 

1049 

1027 996 957 929 840 742 

080C22

High 

2972 2863 2769 2671 2571 2465 2352 2227 2095 1950 

Medium 

High  2173 2146 2103 2082 2036 1966 1904 1827 1738 1621 

Medium 

Low  1670 1667 1647 1618 1585 1549 1492 1408 1350 1238 

Low 

1371 1339 1317 1284 1259 1199 1147 1085 1024  928 

100B12

High 

1258 1278 1283 1259 1240 1204 1149 1073 1015  897 

Medium 

High  986 995 1011 

1003 962 935 913 861 808 738 

Medium 

Low  793 786 786 783 780 750 733 702 627 567 

Low 

667 653 640 629 604 583 558 519 469 427 

100C16

High 

2009 1994 1933 1893 1836 1763 1691 1606 1508 1389 

Medium 

High  1523 1506 1521 1490 1466 1435 1393 1326 1241 1119 

Medium 

Low  1230 1249 1245 1230 1218 1195 1161 1120 1039  949 

Low 

1126 1115 

1095 

1049 

1027 996 957 929 840 742 

100C20

High 

2964 2886 2794 2707 2623 2522 2415 2281 2149 2012 

Medium 

High  2192 2178 2150 2109 2098 2007 1956 1888 1795 1671 

Medium 

Low  1699 1695 1706 1632 1612 1568 1519 1460 1392 1293 

Low 

1361 1356 1337 1304 1267 1243 1191 1149 1077  994 

120C16

High 

1789 1774 1738 1702 1665 1608 1514 1431 1343 1205 

Medium 

High  1451 1445 1431 1413 1394 1362 1312 1235 1149 1037 

Medium 

1202 1210 1266 1252 1226 1191 1082 1028  950  852 

Low 

1063 1050 1033 1010 1007  982  941  889  845  778 

120C20

High 

2828 2768 2699 2612 2524 2423 2308 2219 2118 1982 

Medium 

High  2085 2073 2042 2029 1967 1896 1893 1816 1717 1635 

Medium 

Low  1620 1631 1636 1593 1567 1557 1520 1476 1407 1263 

Low 

1322 1311 1302 1271 1241 1201 1162 1101 1042  979 

130D20

High 

2958 2862 2758 2662 2553 2447 2328 2203 2056 1893 

Medium 

High  2191 2182 2157 2092 2085 1997 1932 1844 1741 1608 

Medium 

Low  1737 1738 1713 1691 1675 1590 1531 1467 1389 1276 

Low 

1404 1394 1380 1355 1327 1276 1220 1163 1095 1013 

Summary of Contents for TM8X*MP Series

Page 1: ...Return 22 Blower Performance CFM Any Position without filter Left Side Return 23 These high efficiency compact units employ induced combustion reli able hot surface ignition and high heat transfer alu...

Page 2: ...abinet support the ends of the furnace rather than lifting by the cabinet flanges at the return air openings bottom or sides or supply air opening 13 When lifting the furnace it is acceptable to use t...

Page 3: ...the National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or for only the NFGC contact the American Gas Association 400 N Capital N W Washington DC 20001 or www NFPA org CANADA NS...

Page 4: ...xide detector with an alarm and battery back up is installed on the floor level where the gas equipment is to be installed In addition the installing plumber or gasfitter shall observe that a battery...

Page 5: ...access cover shall be attached in such a manner as to prevent leaks DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These flanges are rotated down for shipment In order to use...

Page 6: ...uld always be installed on the side desig nated as top side See Figures 4 5 FURNACE ASSEMBLY PC SERIES COILS These upflow coils are designed for installation on top of upflow fur naces only If the coi...

Page 7: ...e unit BOTTOM RETURN AND ATTIC INSTALLATIONS Bottom return applications normally pull return air through a base plat form or return air plenum Be sure the return platform structure or return air plenu...

Page 8: ...15 2 cm minimum clearance between the front of the furnace and the support rods or straps All six suspension points must be level to ensure proper and quiet fur nace operation When suspending the fur...

Page 9: ...stat Wiring FRONT 14 1 1 5 23 SUPPLY END C 24 38 20 5 B Gas Pipe Entry Thermostat Wiring 33 A 5 Electrical Entry Vent Connection Outlet Vent Connection Outlet 4 Diameter Outlet Vent Connection Table 3...

Page 10: ...r side of the furnace using any of the gas pipe entry on both sides of the furnace Refer to Figure 12 All filters and mounting provision must be field supplied All installa tions must have a filter in...

Page 11: ...0 87 0 87 0 81 1000 3 5 3 2 2 9 37 3 0 87 0 80 0 73 1050 3 5 2 9 2 7 39 1 0 87 0 73 0 67 1100 3 2 2 7 2 4 41 0 0 80 0 66 0 61 2500 LP 9 8 8 2 7 5 93 2 LP 2 44 2 03 1 86 PROPANE AND HIGH ALTITUDE CONVE...

Page 12: ...to power auxiliary devices such as humidifiers air cleaners etc The transformer may provide power for an air conditioning unit contactor ACCESSORY CONNECTIONS The furnace control will allow power swi...

Page 13: ...with Hi Efficiency Motor HM1 Humidistat Y Full Stage Compressor G Fan PP11C70224 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Clipping Jumper W914 for electric heat...

Page 14: ...t Numbers SAP Legacy 67297 031 01975 E B E ZD E R OD MODELS HGD HP RHS O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot W1 66 out Heat Y Compressor DEMAND DEFROST CONTROL X L Malfunc...

Page 15: ...mney must extend at least 5 ft 1 5 m above the highest equipment draft hood or flue collar FAN ASSISTED COMBUSTION SYSTEM This appliance is equipped with an integral mechanical means to either draw pr...

Page 16: ...free area Ventilated Combustion Air The ventilated attic space or a crawl space from which the combustion air is taken must comply with the requirements specified in AIR SOURCE FROM OUTDOORS in this i...

Page 17: ...other appliances connected to the venting system are not in operation 1 Inspect the venting system for proper size and horizontal pitch Determine that there is no blockage restriction leakage corrosio...

Page 18: ...non corrosive leak detection fluid or other leak detection methods Take appropriate steps to stop any leak If a leak persists replace the component CALCULATING THE FURNACE INPUT NATURAL GAS Verify na...

Page 19: ...22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 23...

Page 20: ...n and follow the operating instructions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw for the appropriate gas per the following 4 After the mani...

Page 21: ...must be long enough to adequately cool the furnace but not so long that cold air is blown into the heated space The fan off timing may be adjusted by positioning the jumper on two of the four pins as...

Page 22: ...638 2540 2448 2339 2224 2111 1974 1831 Medium High 2234 2233 2147 2092 2042 1974 1907 1820 1705 1575 Medium Low 1722 1716 1690 1681 1603 1553 1489 1426 1335 1241 Low 1396 1375 1348 1325 1263 1200 1150...

Page 23: ...ow 1126 1115 1095 1049 1027 996 957 929 840 742 080C22 High 2972 2863 2769 2671 2571 2465 2352 2227 2095 1950 Medium High 2173 2146 2103 2082 2036 1966 1904 1827 1738 1621 Medium Low 1670 1667 1647 16...

Page 24: ...HI COOL speed when Y1 and Y2 are energized Heating Cycle When the thermostat switch is set on HEAT and the fan is set on AUTO and there is a call for heat a circuit is completed between terminals R a...

Page 25: ...pressure switch hose or faulty pressure switch 4 RED FLASHES This indicates that the main limit switch has opened its normally closed contacts The control will operate the supply air blower and induce...