437642-UIM-C-0210

22

Johnson Controls Unitary Products

NOTES:

1. Airflow expressed in standard cubic feet per minute (CFM).

2. Motor voltage at 115 V.

Table 13: 

Blower Performance CFM - Any Position  (without filter) - Bottom Return

Models

Speed

Bottom Airflow Data (SCFM)

Ext. Static Pressure (in. H2O)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

040A08

High 

966 923 874 804 717 566 386 121  NA  NA 

Medium 

High  813 782 743 687 605 464 280 118  NA  NA 

Medium 

Low  745 706 667 619 545 413 205  NA  NA  NA 

Low 

684 655 614 565 489 342 171  NA  NA  NA 

060A10

High 

1292 

1230 

1160 

1088 

1004 891 760 476 129 129 

Medium 

High 1203 

1157 

1105 

1035 942 846 728 485 133 129 

Medium 

Low 1043 

1010 962 905 823 705 491 305 124 123 

Low 

869 845 811 772 708 579 438 178 145 125 

060A12

High 

1358 1341 1319 1303 1275 1238 1190 1130 1062  943 

Medium 

High  1097 1083 1075 1064 1042 1024  997  962  906  821 

Medium 

Low  935 928 920 899 872 840 809 771 731 659 

Low 

800 779 763 736 711 687 657 622 584 529 

080B12

High 

1329 1307 1285 1247 1195 1143 1091 1027  927  806 

Medium 

High  994 1004 

1008 984 970 941 893 839 773 669 

Medium 

Low  786 790 782 781 761 743 726 685 630 540 

Low 

655 654 647 629 620 594 560 524 469 399 

080C16

High 

1881 1822 1783 1696 1602 1539 1465 1394 1267 1130 

Medium 

High  1553 1535 1492 1456 1408 1343 1279 1226 1113 1014 

Medium 

Low  1312 1286 1288 1260 1205 1143 1091 1029  966  841 

Low 

1169 

1166 

1128 

1098 

1069 

1032 987 909 835 747 

080C22

High 

2811 2725 2638 2540 2448 2339 2224 2111 1974 1831 

Medium 

High  2234 2233 2147 2092 2042 1974 1907 1820 1705 1575 

Medium 

Low  1722 1716 1690 1681 1603 1553 1489 1426 1335 1241 

Low 

1396 1375 1348 1325 1263 1200 1150 1120 1052  965 

100B12

High 

1314 1318 1292 1265 1223 1177  1119 1051  971  890 

Medium 

High 1010 

1004 

1003 995 992 956 914 857 798 721 

Medium 

Low  812 805 796 786 777 754 727 685 626 560 

Low 

661 659 644 623 614 605 568 532 482 399 

100C16

High 

2069 2014 1956 1885 1820 1748 1668 1577 1468 1362 

Medium 

High  1662 1656 1639 1608 1586 1544 1491 1421 1338 1204 

Medium 

1368 1371 1377 1376 1367 1334 1295 1250 1188 1104 

Low 

1016 1014 1018 1030 1012  996  975  944  898  852 

100C20

High 

2893 2774 2687 2589 2478 2376 2255 2120 1978 1824 

Medium 

High  2272 2243 2204 2169 2086 2018 1940 1842 1743 1602 

Medium 

Low  1765 1752 1737 1718 1674 1619 1561 1493 1437 1312 

Low 

1425 1380 1409 1378 1307 1274 1226 1180  1113 1025 

120C16

High 

1752 1724 1702 1664 1600 1542 1454 1372 1264 1119 

Medium 

High  1469 1449 1453 1420 1382 1344 1269 1197  1118 1022 

Medium 

Low  1248 1235 1226 1207 1179 1133 1077  992  922  841 

Low 

1076 1076 1046 1025 1002  968  927  869  784  707 

120C20

High 

2701 2620 2533 2429 2338 2227 2112 1993 1861 1706 

Medium 

High  2125 2083 2046 1994 1955 1901 1857 1737 1621 1497 

Medium 

Low  1664 1664 1647 1619 1580 1555 1468 1392 1332 1226 

Low 

1358 1339 1330 1318 1286 1235 1185 1141 1060  938 

130D20

High 

2823 2714 2613 2507 2399 2282 2170 2042 1908 1761 

Medium 

High  2242 2188 2154 2102 2045 1970 1887 1792 1673 1537 

Medium 

Low  1805 1791 1738 1725 1675 1623 1567 1487 1394 1256 

Low 

1425 1427 1403 1335 1324 1280 1236 1176 1103  996 

Summary of Contents for TM8X*MP Series

Page 1: ...Return 22 Blower Performance CFM Any Position without filter Left Side Return 23 These high efficiency compact units employ induced combustion reli able hot surface ignition and high heat transfer alu...

Page 2: ...abinet support the ends of the furnace rather than lifting by the cabinet flanges at the return air openings bottom or sides or supply air opening 13 When lifting the furnace it is acceptable to use t...

Page 3: ...the National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or for only the NFGC contact the American Gas Association 400 N Capital N W Washington DC 20001 or www NFPA org CANADA NS...

Page 4: ...xide detector with an alarm and battery back up is installed on the floor level where the gas equipment is to be installed In addition the installing plumber or gasfitter shall observe that a battery...

Page 5: ...access cover shall be attached in such a manner as to prevent leaks DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These flanges are rotated down for shipment In order to use...

Page 6: ...uld always be installed on the side desig nated as top side See Figures 4 5 FURNACE ASSEMBLY PC SERIES COILS These upflow coils are designed for installation on top of upflow fur naces only If the coi...

Page 7: ...e unit BOTTOM RETURN AND ATTIC INSTALLATIONS Bottom return applications normally pull return air through a base plat form or return air plenum Be sure the return platform structure or return air plenu...

Page 8: ...15 2 cm minimum clearance between the front of the furnace and the support rods or straps All six suspension points must be level to ensure proper and quiet fur nace operation When suspending the fur...

Page 9: ...stat Wiring FRONT 14 1 1 5 23 SUPPLY END C 24 38 20 5 B Gas Pipe Entry Thermostat Wiring 33 A 5 Electrical Entry Vent Connection Outlet Vent Connection Outlet 4 Diameter Outlet Vent Connection Table 3...

Page 10: ...r side of the furnace using any of the gas pipe entry on both sides of the furnace Refer to Figure 12 All filters and mounting provision must be field supplied All installa tions must have a filter in...

Page 11: ...0 87 0 87 0 81 1000 3 5 3 2 2 9 37 3 0 87 0 80 0 73 1050 3 5 2 9 2 7 39 1 0 87 0 73 0 67 1100 3 2 2 7 2 4 41 0 0 80 0 66 0 61 2500 LP 9 8 8 2 7 5 93 2 LP 2 44 2 03 1 86 PROPANE AND HIGH ALTITUDE CONVE...

Page 12: ...to power auxiliary devices such as humidifiers air cleaners etc The transformer may provide power for an air conditioning unit contactor ACCESSORY CONNECTIONS The furnace control will allow power swi...

Page 13: ...with Hi Efficiency Motor HM1 Humidistat Y Full Stage Compressor G Fan PP11C70224 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Clipping Jumper W914 for electric heat...

Page 14: ...t Numbers SAP Legacy 67297 031 01975 E B E ZD E R OD MODELS HGD HP RHS O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot W1 66 out Heat Y Compressor DEMAND DEFROST CONTROL X L Malfunc...

Page 15: ...mney must extend at least 5 ft 1 5 m above the highest equipment draft hood or flue collar FAN ASSISTED COMBUSTION SYSTEM This appliance is equipped with an integral mechanical means to either draw pr...

Page 16: ...free area Ventilated Combustion Air The ventilated attic space or a crawl space from which the combustion air is taken must comply with the requirements specified in AIR SOURCE FROM OUTDOORS in this i...

Page 17: ...other appliances connected to the venting system are not in operation 1 Inspect the venting system for proper size and horizontal pitch Determine that there is no blockage restriction leakage corrosio...

Page 18: ...non corrosive leak detection fluid or other leak detection methods Take appropriate steps to stop any leak If a leak persists replace the component CALCULATING THE FURNACE INPUT NATURAL GAS Verify na...

Page 19: ...22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 23...

Page 20: ...n and follow the operating instructions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw for the appropriate gas per the following 4 After the mani...

Page 21: ...must be long enough to adequately cool the furnace but not so long that cold air is blown into the heated space The fan off timing may be adjusted by positioning the jumper on two of the four pins as...

Page 22: ...638 2540 2448 2339 2224 2111 1974 1831 Medium High 2234 2233 2147 2092 2042 1974 1907 1820 1705 1575 Medium Low 1722 1716 1690 1681 1603 1553 1489 1426 1335 1241 Low 1396 1375 1348 1325 1263 1200 1150...

Page 23: ...ow 1126 1115 1095 1049 1027 996 957 929 840 742 080C22 High 2972 2863 2769 2671 2571 2465 2352 2227 2095 1950 Medium High 2173 2146 2103 2082 2036 1966 1904 1827 1738 1621 Medium Low 1670 1667 1647 16...

Page 24: ...HI COOL speed when Y1 and Y2 are energized Heating Cycle When the thermostat switch is set on HEAT and the fan is set on AUTO and there is a call for heat a circuit is completed between terminals R a...

Page 25: ...pressure switch hose or faulty pressure switch 4 RED FLASHES This indicates that the main limit switch has opened its normally closed contacts The control will operate the supply air blower and induce...

Page 26: ...L Models Only MISCELLANEOUS ORIFICE BURNER Natural 45 SIGHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft req d GASKET INTAKE PAN PLUG VENT HOLE BRACKET DOOR WIRING HARNESS FERRULE 3 Req d GROMMET 3 Req...

Page 27: ...437642 UIM C 0210 Johnson Controls Unitary Products 27 SECTION X WIRING DIAGRAM FIGURE 25 Wiring Diagram...

Page 28: ...hange without notice Published in U S A 437642 UIM C 0210 Copyright 2010 by Johnson Controls Inc All rights reserved Supersedes 437642 UIM B 0109 Johnson Controls Unitary Products 5005 York Drive Norm...

Reviews: