Installer configuration menu
The thermostat controller comes from the factory with default settings for all configuration
parameters. The UI menu navigation and default settings are shown in Table 13. Before any
outputs turn on, the controller must be configured for the equipment connected. You need to start
from the home screen to perform any of the following tasks.
Screen reset
The current screen returns to the home screen and turns off if the current screen is not touched for
3 minutes. Touch the screen to turn it on again. To disable the screensaving option, press
Display
Settings
and set
Enable Display Timeout
to
No
.
Selecting the unit type
About this task:
The following three unit types are available:
• Four-pipe—This unit type has both heating and cooling coils plus a supply fan. This configuration
can also be used on configurations that are heating or cooling only.
• Two-pipe—This unit type has a single set of pipes that can serve hot or chilled water plus a
supply fan. The Supply Temp Type allows for the connection of an analog sensor or an aquastat
to a binary input. Based on the water temperature or aquastat state, the unit controls heating or
cooling.
• VAV—This unit type is designed for a pressure-dependent zone damper and the supply fan
outputs are disabled. The TEC senses the supply air temperature coming from the unit.
The Supply Temp Type setting allows for the connection of an analog sensor or binary duct
thermostat. Based on the air temperature or duct thermostat state, the zone damper controls for
heating or cooling. The TEC does not control the unit delivering the air. The logic needs to be part
of another controller.
1. Press the
Menu
icon.
2. Press
Setup
.
3. Press
Equipment Setup
.
4. Press
General
.
5. Press
Unit Type
and select
2-pipe
,
4-pipe
, or
VAV
.
6. Press
Save
and the back arrow to return to the previous screen.
Note:
Selecting VAV reboots the controller in order to apply the change.
Selecting the heating and cooling device type
About this task:
By default, the thermostat is configured for On-Off (2-position) control. This can be changed to
Floating (Incremental) mode when the Unit Type is not set to VAV. For VAV mode, only floating actu-
ators are supported and this option is unavailable. To change the Heating/Cooling Device Type:
1. Press the
Menu
icon.
2. Press
Setup
.
3. Press
Equipment Setup
.
4. Press
General
.
27
TEC3000 Series On/Off or Floating Fan Coil Thermostats Installation Guide