Table 4: Terminal identification
Function
Terminal label
1
TEC3012, TEC3013
Floating FC/VAV and
On/Off FC
TEC3312, TEC3313
Floating FC/VAV and
On/Off FC
TEC3612, TEC3613
Floating FC/VAV and
On/Off FC
24 V
24 VAC hot from transformer
FAN H
Fan high
FAN M
Fan medium
FAN L
Fan on (single-speed, variable-speed), Fan low (multi-speed)
AUX
Auxiliary binary output
AUX
Auxiliary power
2
HC/TRI
Cool or heat valve output common
COM
24 VAC common from transformer
CLG O
Cool open (Floating), Cooling NC (On/Off), Triac
CLG C
Cool close (Floating), Cooling NO (On/Off), Triac
HTG O
Heat open (Floating), Heating NC (On/Off), Triac
HTG C
Heat close (Floating), Heating NO (On/Off), Triac
RSEN
Configurable analog input 1
COS
Configurable analog input 2/Changeover binary switch input
VSF
Variable speed fan command (configurable 0 to 10 V range)
BI-2
Configurable binary input 2
BI-1
Configurable binary input 1
NET+
N/A
Not connected
Field bus+/N2+
NET-
N/A
Not connected
Field bus-/N2-
NET COM
N/A
Not connected
Isolated common for
field bus
1
There is no support for an On and Off VAV.
2
HC/TRI on TB1 must be jumpered to COM on TB2 for low-side switching or to 24 VAC on TB2 for high-side switching.
TEC3000 Series On/Off or Floating Fan Coil Thermostats Installation Guide
10