TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions
22
Cal RS
Sets the desired room air sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room temperature.
Default:
0.0F°/0.0C°
Range:
-5.0F°/-2.5C°
to
5.0F°/2.5C°
(adjustable in 1.0F°/0.5C°
increments)
Aux cont
Determines the auxiliary contact
function and configuration.
Default:
0
(0)
Not used,
or used for
reheat
If the Sequence of Operation is set to
reheat (2, 3, or 5), ignore this parameter.
(1)
Auxiliary
N.O.
Occupied = contact
closed
Unoccupied = contact
open
The output
aligns with
occupancy.
(2)
Auxiliary
N.C.
Occupied = contact open
Unoccupied = contact
closed
(3*)
This selection option is not used.
(4*)
This selection option is not used.
(5)
Auxiliary On/Off control through the
auxiliary network command. The output
can be commanded through the network
for any required auxiliary functions via a
separate and dedicated network
variable.
The output
aligns with
the
secondary
network
occupancy
command.
* If option (3) or (4) is selected, the option functions like
option (1) or (2) respectively.
FL time
Sets the maximum actuator stroke
timing (floating
ContrlTyp
TEC2627-2 model).
Default:
1.5 min
Range:
0.5
to
9.0 min
(adjustable in 0.5 minute increments)
Cph
Sets the maximum number of cycles
per hour (on/off
CntrlTyp
TEC2627-2 model).
Default:
4
Range:
3
to
8 cycles per hour
RA/DA
Choice of reverse or direct acting
analog output signal (TEC2647-2
model).
Default:
DA
(RA):
Reverse acting, 0 to 100% = 10 to 0 VDC
(DA):
Direct acting, 0 to 100% = 0 to 10 VDC
Reheat
Sets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the
SeqOpera
parameter).
Default:
0
(1):
10 seconds (six cycles per minute), for various equipment with
solid-state relays that withstand short duty cycles such as electric
heat.
(0):
15 minutes (four cycles per hour), for various equipment with
mechanical relays or contactors controlling mechanical reheat
systems.
UI3 dis
Displays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor).
Default:
-40°F/-40°C
Used as a diagnostic/service help, to troubleshoot and diagnose
sensor operation.
Table 5: Installer Configuration Menu (Part 4 of 4)
Parameter
Appearing
on Display
Description and Default
Selection Options