TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions
10
Cooling (BO1 and BO2) Valve Status
(TEC2627-2 Model)
MSV 67
For On/Off Control:
1 = Open
2 = Closed
For Floating Control:
1 = Stopped
2 = Opening
3 = Closing
BI1 Status
BI 62
0 = Deactivated
1 = Activated
BI2 Status
BI 63
0 = Deactivated
1 = Activated
UI3 Status
BI 64
0 = Deactivated
1 = Activated
Window Alarm
BI 58
0 = Off
1 = On
BI 59
0 = Off
1 = On
Service Alarm
BI 60
0 = Off
1 = On
Occupied Heat Setpoint
3, 7
AV 49
40.0°F/4.5°C to
90.0°F/32.0°C
Occupied Cool Setpoint
AV 50
54.0°F/12.0°C to
100.0°F/37.5°C
Unoccupied Heat Setpoint
AV 51
40.0°F/4.5°C to
90.0°F/32.0°C
Unoccupied Cool Setpoint
AV 52
54.0°F/12.0°C to
100.0°F/37.5°C
Keypad Lockout
MSV 40
1 = Level 0
2 = Level 1
3 = Level 2
4 = Level 3
5 = Level 4
6 = Level 5
BI1 Configuration
MSV 16
1 = None
2 = Rem NSB
3 = Motion NO
4 = Motion NC
5 = Window
BI2 Configuration
MSV 17
1 = None
2 = Door Dry
3 = Override
4 = Filter
5 = Service
UI3 Configuration
MSV 18
1 = None
2 = COC/NH
3 = COC/NC
4 = COS
5 = SS
Menu Scroll
BV 19
0 = No Scroll
1 = Scroll Active
Temperature Scale
BV 21
0 = °C
1 = °F
Table 2: MS/TP Bus Objects (Part 2 of 4)
Point Name
Thermostat Point
(Type/Address)
Range