TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions
11
Out 1 (BO1 and BO2) Configuration
MSV 23
1 = False
2 = True
AUX (BO5) Configuration
MSV 24
1 = Not Used
2 = NO with Occ
3 = NC with Occ
6 = Network Controlled
Heating Setpoint Limit
AV 27
40.0°F/4.5°C to
90.0°F/32.0°C
Cooling Setpoint Limit
AV 28
54.0°F/12.0°C to
100.0°F/37.5°C
Setpoint Type
BV 29
0 = Permanent
1 = Temporary
Temporary Occupancy Time
MSV 30
1 = 0 Hours
2 = 1 Hour
3 = 2 Hours
4 = 3 Hours
5 = 4 Hours
6 = 5 Hours
7 = 6 Hours
8 = 7 Hours
9 = 8 Hours
10 = 9 Hours
11 = 10 Hours
12 = 11 Hours
13 = 12 Hours
14 = 13 Hours
15 = 14 Hours
16 = 15 Hours
17 = 16 Hours
18 = 17 Hours
19 = 18 Hours
20 = 19 Hours
21 = 20 Hours
22 = 21 Hours
23 = 22 Hours
24 = 23 Hours
25 = 24 Hours
Door Time
MSV 31
1 = 1 Minute
2 = 2 Minutes
3 = 3 Minutes
4 = 4 Minutes
5 = 5 Minutes
6 = 6 Minutes
7 = 7 Minutes
8 = 8 Minutes
9 = 9 Minutes
10 = 10 Minutes
Deadband
AV 32
2F°/1C° to
5F°/2.5C°
Reheat Time Base (BO5)
BV 33
0 = 15 Minutes
1 = 10 Seconds
Control Type (TEC2627-2 Model)
BV 35
0 = On/Off
1 = Floating
Table 2: MS/TP Bus Objects (Part 3 of 4)
Point Name
Thermostat Point
(Type/Address)
Range