TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions
21
SeqOpera
Determines the sequence of
operation.
Default:
1
(0):
Cooling Only (Off-Cool). The default is
Cool
.
(1):
Heating Only (Off-Heat). The default is
Heat
.
(2):
Cooling and Reheat (Off-Auto-Heat-Cool). The default is
Heat
.
(3):
Heating and Reheat (Off-Heat). The default is
Heat
.
(4*):
Cool/Heat Four-Pipe (Off-Auto-Heat-Cool). The default is
Heat
.
(5*):
Cool/Heat Four-Pipe and Reheat (Off-Auto-Heat-Cool). The
default is
Heat
.
* Selection option (4.0) for
Out1Conf
only. (See
Out1Conf
parameter
earlier in this table.)
Note:
Choose the selection option
(0): Cooling Only
when using a
changeover sensor to allow changeover to occur between
Cooling Only
and
Heating Only
. Choose the selection
option
(2): Cooling and Reheat
when using a changeover
sensor to allow changeover to occur between
Cooling and
Reheat
and
Heating and Reheat
.
Unocc HT
Sets the Unoccupied Heating
setpoint value.
Default:
62.0°F/16.5°C
Range:
40.0°F/4.5°C
to
90.0°F/32.0°C
Note:
When adjusting the
temperature, press
the
UP/DOWN
arrow keys to
change the
temperature in
0.5F°/0.5C°
increments; press
and hold the
UP/DOWN
arrow
keys to change the
temperature in
5.0F°/5.0C°
increments.
Unocc CL
Sets the Unoccupied Cooling
setpoint value.
Default:
80.0°F/26.5°C
Range:
54.0°F/12.0°C
to
100.0°F/37.5°C
Heat max
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default:
90.0°F/32.0°C
Range:
40.0°F/4.5°C
to
90.0°F/32.0°C
Cool min
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default:
54.0°F/12.0°C
Range:
54.0°F/12.0°C
to
100.0°F/37.5°C
Set type
Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the
UP/DOWN
arrow keys.
Default:
permnent
(temporar):
Local changes to the heating or cooling setpoints are
temporary, and remain effective for the specified TOccTime.
(permnent):
Local changes to the heating or cooling setpoints are
permanently stored in the thermostat memory.
TOccTime
Sets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
•
an Override Function enabled in
the Main User Menu (when the
thermostat is in the Unoccupied
mode)
•
a temporary heating or cooling
setpoint
Default:
2.0 hrs
Range:
0.0
to
24.0 hrs
in 1-hour increments
DoorTime
Engages the Unoccupied mode if
the door stays open minimally for
the time specified.
Default:
2.0 min
Range:
1.0
to
10.0 min
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default:
2.0F°/1.0C°
Range:
2.0F°/1.0C°
to
5.0F°/2.5C°
(adjustable in 1.0F°/0.5C°
increments)
Table 5: Installer Configuration Menu (Part 3 of 4)
Parameter
Appearing
on Display
Description and Default
Selection Options