background image

 

 

Non-Programmable Thermostat Wiring 

TEC2201-2 Single-Stage Thermostat 

The TEC2201-2 features one fan, one heating stage, and one cooling stage. Figure 4 shows a wiring example. 

 

 

Thermostat Terminals – TEC2201-2 

OS

W1

Y1

DI1

G

RS

DI2

RC

C

Scom

RH

 

Jumper J1

Thermostat internal wiring

Jumper J1

System wiring

T1

24 Vac

Cool

Stage 1

Fan

G

Y1

RC

C

Remote

Outdoor

Sensor

Remote

Room

Sensor

Optional

If T2 is not used install jumper J1 across RC and RH.

Field contacts

T2

24 Vac

Digital Input #2

Digital Input #1

RS

Heat

Stage 1

RH

W1

DI2

DI1

OS

Scom

 

Figure 4: TEC2201-2 Single-Stage Thermostat 

TEC2203-2 Multi-Stage Thermostat 

The TEC2203-2 features one fan, two heating stages, and two cooling stages. Figure 5 shows a wiring example. 

Thermostat Terminals – TEC2203-2 

W1

OS

DI1

Y1

Y2

G

RS

DI 2

Scom

RC

C

RH

W2

 

24 Vac

System wiring

Jumper J1

Thermostat internal wiring

T1

24 Vac

Cool

Stage 1

Cool

Stage 2

Y2

Jumper J1

RC

Fan

Y1

G

C

RH

Remote

Outdoor

Sensor

Remote

Room

Sensor

Optional

If T2 is not used install jumper J1 across RC and RH.

Field contacts

T2

Heat

Stage 2

Digital Input #2

Digital Input #1

RS

Heat

Stage 1

W1

W2

DI2

DI1

OS

Scom

 

Figure 5: TEC2203-2 Multi-Stage Thermostat 

4

    TEC220x-2 Series Non-Programmable L

ON

W

ORKS

 Network Configurable Staged Thermostats Installation 

Instructions 

Summary of Contents for TEC2201-2

Page 1: ...o control lighting or disable the economizer function Mechanical Installation Location Install away from any heat source Do not install the thermostat on an outside wall near an air discharge grill in a location affected by direct sun radiation in an area that restrains vertical air circulation to the thermostat coverremoval Figure 1 Bottom of Thermostat Installation To install the thermostat Note...

Page 2: ...auxiliary output is used to toggle occupancy of the electronic control card inside the equipment configure the relay parameter Aux cont to the Normally Open N O setting A second relay can be added for additional functionality of the occupancy output Economizer output uses a half bridge rectifier Reference of the control signal is the common of the power supply of the thermostat terminal C Electrom...

Page 3: ...nfigured as a digital output Max Current 60 mA 12 VDC when configured as digital 200 ohm load 50 mA 10 VDC when configured as analog Protection Auto reset fuse 100 mA 68 F 20 C 0 mA 140 F 60 C Table 3 Thermostat Models Application 1 Heat 1 Cool 2 Heat 2 Cool 2 Heat 2 Cool and Economizer Heat Pump Model Non Programming without Scheduling TEC2201 2 TEC2203 2 TEC2204 2 TEC2202 2 TEC220x 2 Series Non ...

Page 4: ... Figure 4 TEC2201 2 Single Stage Thermostat TEC2203 2 Multi Stage Thermostat The TEC2203 2 features one fan two heating stages and two cooling stages Figure 5 shows a wiring example Thermostat Terminals TEC2203 2 W1 OS DI1 Y1 Y2 G RS DI 2 Scom RC C RH W2 24 Vac System wiring Jumper J1 Thermostat internal wiring T1 24 Vac Cool Stage 1 Cool Stage 2 Y2 Jumper J1 RC Fan Y1 G C RH Remote Outdoor Sensor...

Page 5: ... Mixed Air Sensor MS Scom OS Figure 6 TEC2204 2 Economizer Thermostat TEC2202 2 Heat Pump Thermostat The TEC2202 2 features one fan three heating stages and two cooling stages Figure 7 shows a wiring example Thermostat Terminals TEC2202 2 Y2 DI1 DI2 Y1 RC G O B Scom RS OS RH C W1 24 Vac System wiring Jumper J1 Thermostat internal wiring Compressor Stage 1 T1 24 Vac Compressor Stage 2 Y2 Jumper J1 ...

Page 6: ...to 50ºC 40 to 122ºF Proportional Band for Room temperature Control Both outputs 1 1ºC 2 0ºF Digital Inputs Relay dry contact only across C terminal to DI1 or DI2 Contact Output Rating Each relay output Y1 Y2 G W1 W2 and AU 30 VAC 1 A maximum 30 VAC 3 A in rush Economizer Analog Output Rating 0 to 10 VDC into 2 K ohm resistance minimum Economizer Analog Output Accuracy 3 typical Wire Gauge 18 gauge...

Reviews: