background image

 

11.  Strip each wire 1/4 inch. 

12.  Insert each wire according to wiring diagram. 

13.  Gently push excess wiring back into the hole. 

14.  Install wiring terminals. 

15.  Reinstall the cover (top side first) and gently push 

extra wire length back in the hole in the wall. 

16.  Install security screw. 

te

rm

in

a

lb

lo

c

k

s

 

Figure 3: Security Screw 

Caution 

 

If replacing an old thermostat, label the wires 
before removal of the old thermostat. 

 

Electronic controls are static sensitive devices. 
Discharge yourself properly before installing the 
thermostat. 

 

Short circuits or incorrect wiring may permanently 
damage the thermostat or the equipment. 

 

Anti-short cycling can be set to 0 minutes for 
equipment that possesses its own anti-cycling 
timer. Do not use that value unless the equipment 
is equipped with such internal timer. Failure to do 
so can damage the equipment. 

 

All Thermostat devices are to be used only as 
operating controls. Whenever a control failure 
could lead to personal injury and/or loss of 
property, it becomes the responsibility of the user 
to add safety devices and/or alarm system to 
protect against such catastrophic failures. 

Wiring 

If the same power source is used for the heating 
stages, install jumper across RC and RH. Maximum 
current is 2.0 amperes. 

If auxiliary output is used to toggle occupancy of the 
electronic control card inside the equipment, configure 
the relay parameter (Aux cont ) to the Normally Open 
(N.O.) setting.  A second relay can be added for 
additional functionality of the occupancy output. 

Economizer output uses a half bridge rectifier. 
Reference of the control signal is the common of the 
power supply of the thermostat, terminal C. 

Electromechanical contacts are to be used with the 
digital inputs. Electronic triacs cannot be used as 
mean of switching for the input. The switched leg to 
the input is terminal C (common) 

The transformer of the unit provides power to the 
thermostat and the additional loads that are wired to 
the thermostat. 

Electrical Installation 

Planning and Selecting Cables 

Plan the placement of cables for inputs, outputs, 
communication, and power. 

Place input, output, power, and network cables to 
avoid the effects of ambient noise. 

Separate analog type cables for power, 
communication, inputs, and outputs from other types 
of cables. 

Connectors 

The board connectors accept wires or flat cables: 
22-12 AWG (0.14-2.5 mm²) per pole. 

Table 1: Cable Specifications 

Cable Specification 

Power 

Minimum cable section 18 AWG 

Inputs 

Minimum cable section 20 AWG – twisted pair 

Digital 
Outputs 

Minimum cable section 18 AWG 

Analog 
Outputs 

Minimum cable section 20 AWG – twisted pair 

 

2

    TEC220x-2 Series Non-Programmable L

ON

W

ORKS

 Network Configurable Staged Thermostats Installation 

Instructions 

Summary of Contents for TEC2201-2

Page 1: ...o control lighting or disable the economizer function Mechanical Installation Location Install away from any heat source Do not install the thermostat on an outside wall near an air discharge grill in a location affected by direct sun radiation in an area that restrains vertical air circulation to the thermostat coverremoval Figure 1 Bottom of Thermostat Installation To install the thermostat Note...

Page 2: ...auxiliary output is used to toggle occupancy of the electronic control card inside the equipment configure the relay parameter Aux cont to the Normally Open N O setting A second relay can be added for additional functionality of the occupancy output Economizer output uses a half bridge rectifier Reference of the control signal is the common of the power supply of the thermostat terminal C Electrom...

Page 3: ...nfigured as a digital output Max Current 60 mA 12 VDC when configured as digital 200 ohm load 50 mA 10 VDC when configured as analog Protection Auto reset fuse 100 mA 68 F 20 C 0 mA 140 F 60 C Table 3 Thermostat Models Application 1 Heat 1 Cool 2 Heat 2 Cool 2 Heat 2 Cool and Economizer Heat Pump Model Non Programming without Scheduling TEC2201 2 TEC2203 2 TEC2204 2 TEC2202 2 TEC220x 2 Series Non ...

Page 4: ... Figure 4 TEC2201 2 Single Stage Thermostat TEC2203 2 Multi Stage Thermostat The TEC2203 2 features one fan two heating stages and two cooling stages Figure 5 shows a wiring example Thermostat Terminals TEC2203 2 W1 OS DI1 Y1 Y2 G RS DI 2 Scom RC C RH W2 24 Vac System wiring Jumper J1 Thermostat internal wiring T1 24 Vac Cool Stage 1 Cool Stage 2 Y2 Jumper J1 RC Fan Y1 G C RH Remote Outdoor Sensor...

Page 5: ... Mixed Air Sensor MS Scom OS Figure 6 TEC2204 2 Economizer Thermostat TEC2202 2 Heat Pump Thermostat The TEC2202 2 features one fan three heating stages and two cooling stages Figure 7 shows a wiring example Thermostat Terminals TEC2202 2 Y2 DI1 DI2 Y1 RC G O B Scom RS OS RH C W1 24 Vac System wiring Jumper J1 Thermostat internal wiring Compressor Stage 1 T1 24 Vac Compressor Stage 2 Y2 Jumper J1 ...

Page 6: ...to 50ºC 40 to 122ºF Proportional Band for Room temperature Control Both outputs 1 1ºC 2 0ºF Digital Inputs Relay dry contact only across C terminal to DI1 or DI2 Contact Output Rating Each relay output Y1 Y2 G W1 W2 and AU 30 VAC 1 A maximum 30 VAC 3 A in rush Economizer Analog Output Rating 0 to 10 VDC into 2 K ohm resistance minimum Economizer Analog Output Accuracy 3 typical Wire Gauge 18 gauge...

Reviews: