Technical Specifications
Product
TEC220x-2 Series Non-Programmable L
ON
W
ORKS
Network Configurable Staged
Thermostats
Agency Approvals
FCC Class A - Class A computing device, Subpart J of Part 15
CULus UL873 File E234137 with CCN’s XAPX (US) and XAPX7 (Canada)
Power Requirements
19-30 VAC 50 or 60 HZ; 2 VA (RC and C) Class 2
Ambient Operating
Conditions
0 to 50ºC; (32 to 122ºF) 0 to 95% RH
Ambient Storage
Conditions
-30 to 50ºC; (-22 to 122ºF) 0 to 95% RH
Processor
Neuron® 3120
Communication
LonTalk® Protocol
Transceiver
TP/FT-10; 78 Kbps
Memory
EEPROM
Sensor
Local 10 K NTC thermistor
Resolution
± 0.1
ºC
(±0.2
ºF)
Control Accuracy
±
0.5ºC (
±
0.9ºF) @21ºC (70ºF) typical calibrated
Occupied and Unoccupied
Setpoint Range Cooling
12 to 37.5ºC; (54 to 100ºF)
Occupied and Unoccupied
Setpoint Range Heating
4.5 to 32ºC; (40 to 90ºF)
Room and Outdoor Air
Temperature Range
-40 to 50ºC; (-40 to 122ºF)
Proportional Band for
Room temperature Control
Both outputs: 1.1ºC (2.0ºF)
Digital Inputs
Relay dry contact only across C terminal to DI1 or DI2
Contact Output Rating
Each relay output: (Y1, Y2, G, W1, W2 and AU)
30 VAC, 1 A maximum/30 VAC, 3 A in-rush
Economizer Analog
Output Rating
0 to 10 VDC into 2 K ohm resistance minimum
Economizer Analog
Output Accuracy
±
3% typical
Wire Gauge
18 gauge maximum, 22 gauge recommended
Dimensions
125 mm x 86 mm x 29 mm (4.94” x 3/38” x 1.13”)
Shipping Weight
0.34 kg (0.75 lb)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Controls Group
507 E. Michigan Street
P.O. Box 423
Published in U.S.A.
Milwaukee, WI 53201
www.johnsoncontrols.com
6
TEC220x-2 Series Non-Programmable L
ON
W
ORKS
Network Configurable Staged Thermostats Installation
Instructions