Wiring Analog Outputs
When configured as a digital type, the analog outputs
can provide 60 mA of current for relay, or solid-state
relay, operation.
Table 2: Analog Output Characteristics
Analog Output Characteristic
Voltage
0 to 10 VDC when configured as an
analog output
0 to 12 VDC when configured as a
digital output
Max Current
60 mA @ 12 VDC when configured
as digital (200 ohm load)
50 mA @ 10 VDC when configured
as analog
Protection
Auto-reset fuse:
100 mA @ 68°F (20°C)
0 mA @ 140°F (60°C)
Table 3: Thermostat Models
Application
1 Heat/1 Cool
2 Heat/2 Cool
2 Heat/2 Cool
and Economizer
Heat Pump
Model (Non-Programming
without Scheduling)
TEC2201-2 TEC2203-2 TEC2204-2 TEC2202-2
TEC220x-2 Series Non-Programmable L
ON
W
ORKS
Network Configurable Staged Thermostats Installation
Instructions