Wiring Analog Outputs 

 

When configured as a digital type, the analog outputs 
can provide 60 mA of current for relay, or solid-state 
relay, operation. 

Table 2: Analog Output Characteristics 

Analog Output  Characteristic 

Voltage 

0 to 10 VDC when configured as an 
analog output 

0 to 12 VDC when configured as a 
digital output 

Max Current 

60 mA @ 12 VDC when configured 
as digital (200 ohm load) 

50 mA @ 10 VDC when configured 
as analog 

Protection 

Auto-reset fuse: 

100 mA @ 68°F (20°C) 

0 mA @ 140°F (60°C) 

 

Table 3: Thermostat Models 

Application 

1 Heat/1 Cool 

2 Heat/2 Cool 

2 Heat/2 Cool 
and Economizer 

Heat Pump 

Model (Non-Programming 
without Scheduling) 

TEC2201-2  TEC2203-2 TEC2204-2 TEC2202-2 

 

TEC220x-2 Series Non-Programmable L

ON

W

ORKS

 Network Configurable Staged Thermostats Installation 

Instructions    

3

 

Summary of Contents for TEC2201-2

Page 1: ...o control lighting or disable the economizer function Mechanical Installation Location Install away from any heat source Do not install the thermostat on an outside wall near an air discharge grill in a location affected by direct sun radiation in an area that restrains vertical air circulation to the thermostat coverremoval Figure 1 Bottom of Thermostat Installation To install the thermostat Note...

Page 2: ...auxiliary output is used to toggle occupancy of the electronic control card inside the equipment configure the relay parameter Aux cont to the Normally Open N O setting A second relay can be added for additional functionality of the occupancy output Economizer output uses a half bridge rectifier Reference of the control signal is the common of the power supply of the thermostat terminal C Electrom...

Page 3: ...nfigured as a digital output Max Current 60 mA 12 VDC when configured as digital 200 ohm load 50 mA 10 VDC when configured as analog Protection Auto reset fuse 100 mA 68 F 20 C 0 mA 140 F 60 C Table 3 Thermostat Models Application 1 Heat 1 Cool 2 Heat 2 Cool 2 Heat 2 Cool and Economizer Heat Pump Model Non Programming without Scheduling TEC2201 2 TEC2203 2 TEC2204 2 TEC2202 2 TEC220x 2 Series Non ...

Page 4: ... Figure 4 TEC2201 2 Single Stage Thermostat TEC2203 2 Multi Stage Thermostat The TEC2203 2 features one fan two heating stages and two cooling stages Figure 5 shows a wiring example Thermostat Terminals TEC2203 2 W1 OS DI1 Y1 Y2 G RS DI 2 Scom RC C RH W2 24 Vac System wiring Jumper J1 Thermostat internal wiring T1 24 Vac Cool Stage 1 Cool Stage 2 Y2 Jumper J1 RC Fan Y1 G C RH Remote Outdoor Sensor...

Page 5: ... Mixed Air Sensor MS Scom OS Figure 6 TEC2204 2 Economizer Thermostat TEC2202 2 Heat Pump Thermostat The TEC2202 2 features one fan three heating stages and two cooling stages Figure 7 shows a wiring example Thermostat Terminals TEC2202 2 Y2 DI1 DI2 Y1 RC G O B Scom RS OS RH C W1 24 Vac System wiring Jumper J1 Thermostat internal wiring Compressor Stage 1 T1 24 Vac Compressor Stage 2 Y2 Jumper J1 ...

Page 6: ...to 50ºC 40 to 122ºF Proportional Band for Room temperature Control Both outputs 1 1ºC 2 0ºF Digital Inputs Relay dry contact only across C terminal to DI1 or DI2 Contact Output Rating Each relay output Y1 Y2 G W1 W2 and AU 30 VAC 1 A maximum 30 VAC 3 A in rush Economizer Analog Output Rating 0 to 10 VDC into 2 K ohm resistance minimum Economizer Analog Output Accuracy 3 typical Wire Gauge 18 gauge...

Reviews: