TEC22x4-3 L
ON
W
ORKS
® Networked Multi-Stage Economizer Thermostats Installation Instructions
7
Pwr del
2
Sets the delay time period at
thermostat power up, or at each
time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default:
10.0 sec
Range:
10.0
to
120.0 sec
Frost pr
Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the thermostat.
Default:
off
(on):
Enabled
(off):
Disabled
Heat max
3
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default:
90.0°F/32.0°C
Range:
40.0°F/4.5°C
to
90.0°F/32.0°C
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default:
54.0°F/12.0°C
Range:
54.0°F/12.0°C
to
100.0°F/37.5°C
Anticycl
Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling stages.
Default:
2.0 min
Range:
0.0
to
5.0 min
adjustable in 1-minute increments
Set the anti-short cycle timer to
0.0 min
for equipment that already
has its own anti-short cycle timer.
Heat cph
Sets the maximum number of
Heating cycles per hour.
Default:
4.0
Range:
3.0
to
8.0
cycles per hour
Cool cph
Sets the maximum number of
Cooling cycles per hour.
Default:
4.0
Range:
3.0
or
4.0
cycles per hour
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default:
2.0F°/1.0C°
Range:
2.0F°/1.0C°
to
4.0F°/2.0C°
adjustable in 1.0F°/0.5C°
increments
Fan cont
Determines how the fan is activated
in response to a call for heating.
Fan cont
applies to W1 & W2 and
Fan Mode
auto only
.
Fan cont
does not affect fan operation on a
call for cooling (Y1 & Y2).
Default:
on
(off):
The thermostat will not activate the fan in response to a call
for heating. The fan is activated by the equipment fan and limit
control.
(on):
Enables the thermostat to activate the fan in response to a call
for heating or cooling.
Fan del
Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default
off
(on):
Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off):
No extension of fan operation after a heating or cooling cycle
has ended.
The fan delay is only active when the fan is in the Auto mode.
Table 2: Installer Configuration Menu (Part 2 of 5)
Parameter
Appearing
on Display
Description and Default
Selection Options