background image

TEC22x4-3 L

ON

W

ORKS

® Networked Multi-Stage Economizer Thermostats Installation Instructions

4

Connecting the L

ON

W

ORKS

 Network

The wiring rules for the L

ON

W

ORKS

 network differ from 

the wiring rules for the Metasys® N2 Bus and the 
BACnet® Master-Slave/Token Passing (MS/TP) Bus. 
For more details on wiring the L

ON

W

ORKS

 network, 

refer to the 

L

ON

W

ORKS

 Network Layout Technical 

Bulletin (LIT-1162150)

.

To connect the thermostat to the L

ON

W

ORKS

 network:

1.

Connect the L

ON

W

ORKS

 network wires to the 

L

ON

W

ORKS

 network terminal block on the 

thermostat (Figure 5, Figure 6, and Figure 7).

Note:

There is no polarity when connecting the 

L

ON

W

ORKS

 network wires to the thermostat; however, 

we recommend keeping the polarity consistent 
throughout the network. 

2.

After the L

ON

W

ORKS

 network wires are connected 

to the first thermostat, continue in a daisy-chained 
fashion to the next device.

Note:

The L

ON

W

ORKS

 network wiring must be twisted-

pair lines.

Do not run the L

ON

W

ORKS

 network wiring in the same 

conduit as line voltage wiring (30 VAC or above) or 
other wiring that switches power to highly inductive 
loads (such as contactors, coils, motors, or 
generators).

The L

ON

W

ORKS

 network requires proper termination 

and biasing at the end of a segment (a segment is a 
physically continuous length of wire). The thermostat is 
not equipped with the ability to provide this termination; 
therefore, it cannot be located at the physical end of a 
L

ON

W

ORKS

 network segment unless a terminator is 

attached. Refer to 

L

ON

W

ORKS

 Network Layout 

Technical Bulletin (LIT-1162150)

 for end-of-line 

solutions.

Setup and Adjustments

Thermostat Operation Overview

Thermostat User Interface Keys

The TEC22x4-3 thermostat user interface consists of 
five keys on the front cover (as illustrated in Figure 8). 
The function of each key is as follows:

Use  the 

YES/SCROLL

 key to:

-

confirm menu selections and to advance to the 
next menu item

-

stop the Status Display Menu from scrolling 
and to manually scroll to the next parameter on 
the menu

Note:

When the thermostat is left unattended for 

45 seconds, the thermostat display resumes scrolling.

Use  the 

NO

 key to decline a parameter change and 

to advance to the next menu item.

Figure 7: Thermostat to Network Connection

Supervisory 

Controller

Twist wires together 
before inserting them into 
the terminals.

F

IG

:L

O

N

_

w

ir

L

W

ON

ORKS

 

Network Wires

L

W

ON

ORKS

Network 

Terminal Block

L

W

 

Bus Terminals

ON

ORKS

Figure 8: Front Cover of Thermostat

70.0ºF

Room Temp

YES

NO

Backlit, plain text

LCD is easy to read

in any condition.

Five keys on the thermostat
make operation easy and intuitive.

LEDs indicate
system activity.

F

IG

:f

rn

t_

v

w

Summary of Contents for TEC22 4-3 Series

Page 1: ...nt Regulations Cet appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x4 3 thermosta...

Page 2: ...efully snap it into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an exist...

Page 3: ...7 8 9 10 11 12 13 14 15 16 Figure 6 Wiring the TEC22x4 3 Thermostats FIG TEC22x4_wrng 24 VAC Thermostat Power Y2 Y1 RC EC C If using the same power source for the thermostat and heating loads install...

Page 4: ...of a segment a segment is a physically continuous length of wire The thermostat is not equipped with the ability to provide this termination therefore it cannot be located at the physical end of a LO...

Page 5: ...Configuration Menu is used to set up the thermostat for application specific operation To access this menu press and hold the MENU key for approximately 8 seconds Configuring the TEC22x4 3 Thermostats...

Page 6: ...thermostat RemNSB Remote Night Setback NSB via a time clock input an occupancy sensor or from a voltage free contact Contact open Occupied contact closed Unoccupied DI21 Configuration of Digital Inpu...

Page 7: ...cycle timer Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 o...

Page 8: ...H stage Reverts the operation of a two stage thermostat to a single stage thermostat when the second heating stage is not needed Default 2 0 1 0 One Stage 2 0 Two Stages C stage Reverts the operation...

Page 9: ...fault 55 0 F 13 0 C Range 14 0 F 10 0 C to 70 0 F 21 0 C Min pos Sets the minimum position for the OA dampers on the economizer These dampers are energized to minimum position when the fan Terminal G...

Page 10: ...e To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied override state this is the first...

Page 11: ...tus Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the display it may be the first prompt Press the YES key to enter the temp...

Page 12: ...event parameter during the configuration process If the schedule setting menu does not reflect a two event schedule select two events in the 2 4event parameter of the Installer Configuration Menu When...

Page 13: ...prompt appears on the display Press the YES key to enter the scheduling menu Table 4 Programming the Daily Schedule Two Event Part 2 of 2 Thermostat Display Description Wednesda set Y N Exit Y N RoomT...

Page 14: ...ayed press the YES key to store the day 6 Press the YES key to choose the time format or press the NO key to access the Main User Menu exit prompt 7 Press the UP DOWN arrow keys to select the desired...

Page 15: ...ly voltage between RC and C is in the range of 19 to 30 VAC Check for tripped fuse or circuit breaker Overloaded power transformer Verify that the transformer used is powerful enough enough VAs to sup...

Page 16: ...igital Inputs DI1 or DI2 Filter Indicates that the filter s is dirty in accordance with the programmable Digital Inputs DI1 or DI2 Frost ON Indicates that the heating is energized by the low limit fro...

Page 17: ...g and Regulating Equipment FCC Compliant to CFR 47 Part 15 Subpart B Class A LONMARK Certification 3 4 pending Canada UL Listed File E27734 CCN XAPX7 Under CAN CSA C22 2 No 24 Temperature Indicating a...

Reviews: