TEC22x4-3 L

ON

W

ORKS

® Networked Multi-Stage Economizer Thermostats Installation Instructions 

9

Aux cont

Energizes peripheral devices 
(lighting equipment, exhaust fans, 
and economizers).
Default: 

n.o.

(n.c.):

 Contact open = Occupied; contact closed = Unoccupied

(n.o.):

 Contact closed = Occupied; contact open = Unoccupied

The contact toggles with the internal Occupied/Unoccupied 
schedule (or the NSB contact on one of the digital inputs, if used).

Prog rec

4

Provides the desired occupied 
temperature either at the start of the 
occupied schedule or after the 
occupied schedule begins.

Note:

Progressive recovery is 
disabled if either DI1 or DI2 
is configured as remote NSB

Default: 

off

(on):

 Enabled (provides the desired occupied temperature at the 

start of the occupied schedule)

(off):

 Disabled (provides the desired occupied temperature after the 

occupied schedule begins)

Chngstpt

3

Sets the economizer changeover 
strategy, based on the outdoor air 
temperature. Requires that an 
outdoor air temperature sensor be 
installed and connected.
When the OA temperature is below 
the changeover setpoint, free 
cooling is used (economizer 
operation). When the OA 
temperature is above the setpoint, 
mechanical cooling is used 
(compressor operation).
Default:  

55.0°F/13.0°C

Range: 

14.0°F/-10.0°C

 to 

70.0°F/21.0°C

Min pos

Sets the minimum position for the 
OA dampers on the economizer. 
These dampers are energized to 
minimum position when the fan 
(Terminal G) is energized and the 
thermostat is in the Occupied mode. 
When the schedule is in the 
Unoccupied mode, the minimum 
position is 0%.
Default: 

0.0%

Range: 

0.0

 to 

100.0%

 equals 0 to 10 VDC output range

% OA

Setting for

0 to 10 VDC

Actuator

Setting for

2 to 10 VDC 

Actuator

(0.0%)

0%

0 to 20%

(5.0%)

5%

24%

(10.0%)

10%

28%

(15.0%)

15%

32%

(20.0%)

20%

36

%

(25.0%)

25%

40%

(30.0%)

30%

44%

C mech

Determines whether to allow 
mechanical cooling (compressor 
operation) if free cooling 
(economizer operation) cannot 
maintain the cooling setpoint.
Default: 

off

(on):

 Typically applies when the MS is installed before the 

mechanical cooling refrigeration coils in the mixing plenum. In this 
scenario, mechanical cooling is allowed when free cooling cannot 
maintain the cooling setpoint.

(off):

 Typically applies when the remote Mixed air Sensor (MS) is 

installed after the mechanical cooling refrigeration coils. In this 
scenario, mechanical cooling will never operate at the same time as 
free cooling.

Mix stpt

3

Establishes the mixed air 
temperature when operating in the 
economizer mode.
Default: 

55.0°F/13.0°C

Range: 

50.0°F/10.0°C

 to 

90.0°/32.0°C

Table 2:  Installer Configuration Menu  (Part 4 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Summary of Contents for TEC22 4-3 Series

Page 1: ...nt Regulations Cet appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x4 3 thermosta...

Page 2: ...efully snap it into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an exist...

Page 3: ...7 8 9 10 11 12 13 14 15 16 Figure 6 Wiring the TEC22x4 3 Thermostats FIG TEC22x4_wrng 24 VAC Thermostat Power Y2 Y1 RC EC C If using the same power source for the thermostat and heating loads install...

Page 4: ...of a segment a segment is a physically continuous length of wire The thermostat is not equipped with the ability to provide this termination therefore it cannot be located at the physical end of a LO...

Page 5: ...Configuration Menu is used to set up the thermostat for application specific operation To access this menu press and hold the MENU key for approximately 8 seconds Configuring the TEC22x4 3 Thermostats...

Page 6: ...thermostat RemNSB Remote Night Setback NSB via a time clock input an occupancy sensor or from a voltage free contact Contact open Occupied contact closed Unoccupied DI21 Configuration of Digital Inpu...

Page 7: ...cycle timer Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 o...

Page 8: ...H stage Reverts the operation of a two stage thermostat to a single stage thermostat when the second heating stage is not needed Default 2 0 1 0 One Stage 2 0 Two Stages C stage Reverts the operation...

Page 9: ...fault 55 0 F 13 0 C Range 14 0 F 10 0 C to 70 0 F 21 0 C Min pos Sets the minimum position for the OA dampers on the economizer These dampers are energized to minimum position when the fan Terminal G...

Page 10: ...e To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied override state this is the first...

Page 11: ...tus Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the display it may be the first prompt Press the YES key to enter the temp...

Page 12: ...event parameter during the configuration process If the schedule setting menu does not reflect a two event schedule select two events in the 2 4event parameter of the Installer Configuration Menu When...

Page 13: ...prompt appears on the display Press the YES key to enter the scheduling menu Table 4 Programming the Daily Schedule Two Event Part 2 of 2 Thermostat Display Description Wednesda set Y N Exit Y N RoomT...

Page 14: ...ayed press the YES key to store the day 6 Press the YES key to choose the time format or press the NO key to access the Main User Menu exit prompt 7 Press the UP DOWN arrow keys to select the desired...

Page 15: ...ly voltage between RC and C is in the range of 19 to 30 VAC Check for tripped fuse or circuit breaker Overloaded power transformer Verify that the transformer used is powerful enough enough VAs to sup...

Page 16: ...igital Inputs DI1 or DI2 Filter Indicates that the filter s is dirty in accordance with the programmable Digital Inputs DI1 or DI2 Frost ON Indicates that the heating is energized by the low limit fro...

Page 17: ...g and Regulating Equipment FCC Compliant to CFR 47 Part 15 Subpart B Class A LONMARK Certification 3 4 pending Canada UL Listed File E27734 CCN XAPX7 Under CAN CSA C22 2 No 24 Temperature Indicating a...

Reviews: